Software Release History
|
Boiler Controller
|
|
BLR / DIN / STD/ ...BLR / DIN / HIL/ ... |
PROM file header: BLRVT (SH/001 and /003 variants)
Software Version | Release Date | Further Information | Notes |
4d1
|
01/04/05 |
Feature Notes
|
add support for modulating condensing boilers
|
4c6
|
19/05/04 |
Feature Notes
|
fix bug on alarms whereby local hi/lo boilers only shut down one stage on alarm |
4c5
|
22/11/02 |
0004/0002 C5 |
correct serial eeprom driver so that MicroChip parts can be used |
4c4config tables |
06/08/02 |
0004/0002 C5 |
add support for registering Mitsubishi LMAP interface
|
4c3config tables |
08/10/01 |
0004/0002 C5 |
add SUSPEND BACKROUND comms to improve configuration comms response rateremove redundant network variables to save space.NOT on general release, used on Granta Park |
4c2config tables |
20/12/00issue notes |
0004/0002 C5 |
add Minimum VT Flow parameter for systems without a proper Primary Circuit |
4c1config tables |
01/11/00issue notes |
0004/0002 C5 |
major new release
|
3d5config tables |
11/06/99 |
0004/0001 C4 |
change registration of SLT to be subnet 30 in line with other issue 4 registration devices |
3d4 |
01/06/99 |
0004/0001 C4 |
correct registration of networked sensors |
3d2 |
01/03/99 |
0004/0001 C4 |
correct registration error, group address set up in non boiler sub modules when boiler in config during registration. Could be cause of unexplained 'broken registration links'. |
3d1 |
26/01/99 |
0004/0001 C4 |
change no demand shut down routine to be compatible with issue 4a Zone controllers. Boiler will shut down if no network variable demands have been received for 5 minutes. |
3c9
|
20/11/98issue notes |
0004/0001 C4 |
add defensive restart on control loop timer could be solution for mysterious Boiler inaction |
3c8 |
20/11/98 |
0004/0001 C4 |
add parameter to display VT temperature |
3c7 |
02/11/98 |
0004/0001 C4 |
change made to boiler sequence to re-try failed boilers |
3c6 |
26/10/98issue notes |
0004/0001 C4 |
allow registration of monitor modules with the boiler both in and out of config mode |
3c5 |
20/10/98 |
0004/0001 C4 |
serious bug introduced in 3c4 when utilising both flow and return sensor, use this version. |
3c4config tables |
19/10/98issue notes |
0004/0001 C4 |
Alarms enhanced. Minor correction to compensator calculation.VT valve hunting in frost condition corrected.Minor correction to registration of secondary heat/cool sources, number of status lamp flashes on device being registered. |
3c3 |
25/07/98issue
|
0004/0002 C4 |
correct registration of sub modules |
3c2 |
10/07/98issue
|
0004/0002 C4 |
add registration support for Alarm Monitor modules correct reporting of Zone Demand |
3c1config tables |
05/06/98issue
|
0004/0002 C |
add degC/degF support add ability to disable Flow temperature Boostadd no comms reset add configurable plotsadd monitoring of 'summer cut off'correct operation of run on timers |
3b2 |
29/05/98issue
|
0004/0002C |
add support for disabling 'replace node' |
3b1 |
24/11/97 |
0004/0002 C |
change registration routine to support Fan Coils |
3a6 |
03/10/97 |
0004/0002 C |
add AHU registration support |
3a1 |
10/09/97 |
0004/0002 C |
new issue boards only add alarm code notesadd frost alarm |
BV2v |
03/03/97 |
B |
add CRNG, TRNG to limit operation of COMP adjustment and zone trim add MIND minimum demand so boiler can be set to run for all of occupation period |
BV2u |
21/01/97 |
B |
improve operation of comp_differential, do not adjust if limited by VMAX correct initial Boiler Flow setpoint when zone first becomes occupied old notes_2g old_notes_2s old_notes_2t |
Software Release Document for: BLR/DIN/STD and /HIL (NH/004 and /006 variants)
PROM file header: HSCBV (NH/004 and /006 variants)
Software Version | Release Date | Hardware Version | Notes |
4c5
|
16/01/04 |
0004/0002 C5 |
correct serial eeprom driver so that MicroChip parts can be used |
3d4 | 11/05/99 | 0004/0002 C5 |
change sub module mix to 2 cascade plus 1 PCO |
3d2 | 15/03/99 | 0004/0002 C5 | bring into line with Primary Boiler issue |
3b1 | 30/03/98 | 0004/0002 C5 | change registration routine to support Fan Coils |
3a6 | 03/10/97 | 0004/0002 C5 | add AHU registration support |
3a1 | 10/09/97 | 0004/0001 C4 | new issue boards only
add alarm code add frost alarm |
BV2v | 03/03/97 | B | add CRNG, TRNG to limit operation of COMP adjustment and
zone trim
add MIND minimum demand so boiler can be set to run for all of occupation period |
BV2v | 03/03/97 | B | add CRNG, TRNG to limit operation of COMP adjustment and
zone trim
add MIND minimum demand so boiler can be set to run for all of occupation period |
BV2u |
21/01/97 |
B | improve operation of comp_differential, do not adjust if
limited by VMAX
correct initial Boiler Flow setpoint when zone first becomes occupied |