Configuration Parameters - Boiler Controller

Types:BLR/DIN/STD/xxx

Software Release: BLRVT4c1

Configuration Parameters

ref   Description default range
C1 FRST Frost protection level

Can disabled by setting FRST = 0 - (see Data Sheet for details)

3 2 to 15
C2 MAXF Maximum flow water temperature 80 30 to 110
C3 MINR Minimum return water temperature 40 10 to 50
C4 FLAV VT water temperature at 10°C outside temperature 50 20 to 80
C5 SACT Sensor Action

0 = use flow or return water sensors, if both present use average

1 = use flow water sensor

2 = use return water sensor

3 = average of flow and return water sensors

1 1 to 3
C6 BLRS Total number of boilers/stages available in sequence 2 1 to 8
C7 MXVT Maximum VT circuit water temperature 60 20 to 100
C8 VLIM Limits opening of the VT circuit valve if the return water temperature is below MINR.

Limiting is proportional over the band MINR to MINR-10°C.

0 = Valve will close fully if return < MINR-10°C

20 = Valve will close to 20% if return < MINR-10°C

100 = Limiting disabled, valve will follow demand.

100 0 to 100
C9 DHWP Domestic hot water priority

0 = Hot water and Heating have equal prioity

1 = Hot water has priority, VT pump will shut down when DHW requires heating

0 0 to 1
C10 MIN Boiler minimum run time 5 1 to 20 (minutes)
C11 BRON Primary pump run after all boilers off 1 0 to30

(minutes)

C12 PERD VT circuit valve stroke time 18 (180sec) 2 to 60 secs/10
C13 TRNG Flow setpoint trim, proportional effect from Zone demands 10 0 to 20
C14 CRNG Flow setpoint trim, adaptive effect from Zone demands 10 0 to 20
C15 MODE Zone actuator/valves operation

0 = actuators/valves match their zone heat demand

1= VT circuit forced on with valve fully open while boiler shut down in progress.

2 = as for 1 plus zone with highest heating demand sets actuator/valve 100%, other zones ratio output dependant on their heat demand. All actuators/valves open fully in BRON period (heat dissaption)

0 0 to 2
C16 BLOK Boiler stages available (i.e.. not in fault condition)   0 to 8
C17 AREM All boilers remote

0 = Boiler outputs on controller are included in sequence

1 = All boiler stages are via cascade modules. Boiler outputs on controller not used

0 0 to 1
C18 SMRT Summer heating inhibit if outside temperature > SMRT 18 10 to 30
C19 MIND Minimum zone demand for boilers to run:

0: heating runs to heating setpoint for Occupation period

2 0 to 10
C20 COMP Compensator offset 0 -50 to 50
C21 ALRM Alarm mode:
  • 0: No Alarms generated, no control action on event
  • 1: No Alarms generated, but disable boiler on event
  • 2: Generate LOKA/B Lockout Alarm and disable boiler on fault
  • 3: Generate GENA/B General Alarm but do not disable boiler on fault
  • 4: Generate STOP alarm if input ‘a’ in alarm condition (input ‘b’ operates as General alarm)
  • 5:Generate STOP alarm if input a in alarm condition, input b GENB shuts down Boiler if in alarm, used for pressurisation fault.


0


0 to 5
C22 ALST Alarm state

0 = Open circuit indicates Alarm

1 = Closed circuit indicates Alarm


0

0 to 1
C23 TYPE Output type : Not available from Zone Controller (Doorway only). Factory set to:
1 = Normal sequencing of stages

3 = Fixed sequencing of stages

1 0 to 3

Monitoring Parameters

ref   Description default range
    INPUTS    
I1 (C30) INPA Fault input 1 status   0 to 1
I2 (C31) INPB Fault input 2 status   0 to 1
I3 (C32) BLRA Boiler 1 output status   0 to 1
I4 (C33) BLRB Boiler 2 output status   0 to 1
I5 (C34) PPMP Primary pump output status   0 to 1
I6 (C35) VTOP VT valve open output status   0 to 1
I7 (C36) VTCL VT valve close output status   0 to 1
I8 (C37) VPMP VT pump output status   0 to 1
         
         
    SWITCHES    
W1

(C38)

AUTO Controller in automatic control 1 0 to 1
W2

(C39)

OVRD Override

W1 and W2 used together with Doorway Auto/manual dialog box

n/a 0 to 1
W3

(C40)

SHOF Summer Heating Inhibit in Operation (Read Only)

1 = Heating disabled

n/a 0 to 1
W4

(C41)

ZBST Zone boost disable - Use weather compensation only.

0 = Zone Boost disabled

1 0 to 1
W5

(C42)

HAND manual HAND mode from InSite, VT demand set on MANL C83 0 0 to 1
W6

(C43)

RPLN Replace missing nodes in database

1 = Auto replace node

1 0 to 1
W7

(C44)

SERV Generate Service Pin Message

 

0 0 to 1
W8

(C45)

CGST Configuration mode 0 0 to 1
    SENSORS    
S1 (C50) FLOW Flow water temperature   0 to 110 °C
S2 (C51) RTRN Return water temperature   0 to 110 °C
S3 (C52) VTMP VT circuit temperature   0 to 110 °C
S4 (C53) OUTS Outside temperature   0 to 110 °C
S5 (C54) FLSP Current flow setpoint   0 to 100 °C
S6 (C55) BLOP Current boiler(s) demand level   0 to 100
S7 (C56) VTPN VT valve position   0 to 100
S8 (C57) ZDMD Zone demand   0 to 100
S9 (C58) VTSP VT setpoint   0 to 100 °C
    KNOBS    
K1 (C60) MAXF Maximum flow temperature 80 0 to 100°C
K2 (C61) MINR Minimum return temperature 40 0 to 100°C

  The following parameters are available only from Doorway Supervisor:

Control loop parameters - SeaChange Use only

ref   Description default range
C69 FDIV divisor for Boiler flow tracking control 30 5 to 250
C70 UNDF sets very Low muzzy level for boiler loop   9 20 to 250
C71 OVRF sets very High muzzy level for boiler loop 9 20 to 250
C72 DBDF deadband sets limit for OK band for boiler loop 5 20 to 250
C73 PGNF proportional gain boiler 0 0 to 250
C74 GN F gain boiler 5 1 to 250
C75 UNDV sets very Low muzzy level for VT loop 9 20 to 250
C76 OVRV sets very High muzzy level for VT loop 9 20 to 250
C77 DBDV deadband sets limit for OK band for VT loop 5 20 to 150
C78 PGNV proportional gain variable circuit temp 0 0 to 250
C79 GN V gain variable temperature circuit 1 1 to 250

 

System parameters

ref   Description default range
C80 XCFG Force others exit config n/a 0 to 1
C81 GRP own group address n/a 0 to 255
C82 CSTP Enable remote application restart n/a 0 to 99
C83 MANL manual level 0 -100 to 100
C84 NCRS No communications number of restarts n/a 0 to 255
C85 SWRS Non power up restarts n/a 0 to 256
C86 ADCE adc errors n/a 0 to 255

Alarm parameters

ref   Description default range
C90 NOAL No Alarms n/a 0 to 1
C91 GENA General alarm A n/a 0 to 1
C92 GENB General alarm B n/a 0 to 1
C93 LOKA Lockout alarm A n/a 0 to 1 
C94 LOKB Lockout alarm B n/a 0 to 1
C95 FREZ Danger of freezing alarm n/a 0 to 1
C96 STOP Master stop alarm (firelink) n/a 0 to 1
C97 OUTF Outside temperature fail n/a 0 to 1
C98 FROS Frost Protection in progress n/a 0 to 1
C99 DPMF Dual Pump fail n/a 0 to 1

 

Number of registered devices

ref   Description default range
C100 CAS Numer of Cascade module n/a 0 to 8
C101 ZONE Number of Zone's n/a 0 to 100
C102 PCO Number of Pump change over modules n/a 0 to 3
C103 SUPV Number of Supervisors n/a 0 to 8 
C104 HSC Number of Heat Sources n/a 0 to 20
C105 CSC Number of Cool sources n/a 0 to 20
C106 AHU Number of Air Handlers n/a 0 to 50
C107 OUTS Number of Outside Sensors n/a 0 to 1
C108 MON Number of Monitoring Modules n/a 0 to 10
C109 RTR Number of Routers n/a 0 to 4

 

Own Heat & Cool source parameters

ref   Description default range
C120 TEST Test mode 0 0 to 255
C121 HSCN Boilers own heat source number 1 1
C122 CSCN Boilers own cool source number 0 0

Plot parameters

ref   Description default range
C130 PN A config variable number for channel A 51 0 to 255
C131 PT A period code for plot A 1 1 to 4
C132 PN B config variable number for channel B 52 0 to 255
C133 PT B period code for plot B 1 1 to 4
C134 PN C config variable number for channel C 53 0 to 255
C135 PT C period code for plot C 1 1 to 4
C136 PN D config variable number for channel D 54 0 to 255
C137 PT D period code for plot D 1 1 to 4