Configuration Tables

Boiler Controller
with VT Circuit (STD) and
Hi/Lo Fired with VT Circuit (HIL)

Latest released version is 4d1

Changes in this issue are RED in text

BLR / DIN / STD/ ...

BLR / DIN / HIL/ ...

 

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
FRST
Frost Protection / Non Occupied Setpoint
Deg C
3
2 to 15
C2
MAXF
Maximum Primary Setpoint
Deg C
80
30 to 110
C3
MINR
Minimum Return Setpoint
Deg C
40
10 to 50
C4
FLAV
Flow Temperature for 10°C outside temperature
Deg C
50
20 to 100
C5
SACT
Sensor Action
0: Use flow or return, or average if both sensors valid
1: Use flow sensor value
2: Use return sensor value
3: Use average of flow and return sensor values
-
1
0 to 3
C6
BLRS
Number of boilers in sequence
-
2
1 to 8
C7
MXVT
Maximum VT circuit water temperature
Deg C
80
20 to 100
C8
VLIM
Limits the opening of VT valve if return temp is below MINR
0%: Valve will close fully if Return > 10 Deg C below MINR
50%: Valve will close 50% if Return > 10 Deg C below MINR
100%: Valve will control normally, no limitation
%
100
0 to 100
C9
DHWP
Hot Water Priority:
0: Hot water and heating have equal priority
1: VT valve closes when DHW is demanding heat
-
0
0 to 1
C10
MIN
Boiler minimum run time
Mins
5
1 to 20
C11
BRON
Primary pump run on time
Mins
5
0 to 30
C12
PERD
VT valve stroke time
Secs/10
18
2 to 60
C13
TRNG
Maximum trim effect on heating setpoint
Deg C
10
0 to 20
C14
CRNG
Maximum adaptive effect on heating setpoint
Deg C
10
0 to 20
C15
MODE
Mode select:
0: VT Valve held shut while Primary Pump only runs on
Actuator demands match zone heat demand
1: VT Valve opened while Primary and VT Pumps run on
Actuator demands match zone heat demand
2: VT Valve opened while Primary and VT Pumps run on
All actuators opened proportional to highest zone demand
Note in non-Housekeeping Boiler Controllers this parameter is fixed MODE=0.
-
0
0 to 2
C16
BLOK
Number of boiler stages available to run (i.e. not locked out)
-
read only
0 to 8
C17
AREM
All boilers remote
0: Boiler outputs on controller included in sequence
1: All boiler stages via cascade modules
Boiler Controller outputs disabled
-
0
0 to 1
C18
SMRT
Summer heating inhibit if outside temperature > SMRT
Deg C
20
10 to 30
C19
MIND
Minimum Demand for Boiler Controller to operate
0: When demand drops to zero, boilers and pumps continue to run
MIND > 1: When demand drops to zero, boilers and pumps stop
%
2
0 to 10
C20
COMP
Compensator offset
Deg C
0
-50 to 50
C21
ALRM
Alarm Mode
0: Ignore alarms
1: Disable Boiler outputs, no alarm (maintenance switches)
2: Report all alarms, continue running (lockout alarms)
3: Report all alarms, continue running (general alarms)
4: Report all alarms, shut down on STOP alarm only
5: Report all alarms, shut down on STOP alarm or “Master Off”
-
0
0 to 5
C22
ALST
Alarm report sense
0: Alarm if input = 0 (contact open)
1: Alarm if input = 1 (contact closed)
-
1
0 to 1
C23
DOMN
Own Domain (for SH types only)
-
0
0 to 8
C24
TYPE
Output type : Not available from Zone Controller (Doorway only). Factory set to:
1 = Normal sequencing of stages
3 = Fixed sequencing of stages
-
1
0 to 3
C25
MNVF
Minimum VT Flow: used to ensure a minimum opening on the VT valve while the boilers are running. This only needs to be used when the Boiler does not have a pumped primary circuit or shunt circuit.
%
0
0 to 100
C26
DMOR
Demand Override:
when set and ALRM is 0 or 3, an alarm generated on input a will disable all demands VT & CT to the Boiler
-
0
0 or 1

 

 

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
INPA
External input ‘a’ status
-
-
0 to 1
I2 (C31)
INPB
External input ‘b’ status
-
-
0 to 1
I3 (C32)
BLRA
Boiler 1 output status
-
-
0 to 1
I4 (C33)
BLRB
Boiler 2 output status
-
-
0 to 1
I5 (C34)
PPMP
Primary pump output status
-
-
0 to 1
I6 (C35)
VTOP
VT valve open output status
-
-
0 to 1
I7 (C36)
VTCL
VT valve close output status
-
-
0 to 1
I8 (C37)
VPMP
Secondary pump output status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
SHOF
Summer heating (inhibited if SHOF = 1)
-
read only
0 to 1
W4 (C41)
ZBST
Zone boost (disabled if ZBST = 0)
-
1
0 to 1
W5 (C42)
HAND
Manual HAND mode
-
0
0 to 1
W6 (C43)
RPLN
Replace missing nodes in Database (for SH types only)
-
1
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
FLOW
Flow Temperature
Deg C
-
-
S2* (C51)
RTRN
Return Temperature
Deg C
-
-
S3* (C52)
VTMP
VT circuit Temperature
Deg C
-
-
S4* (C53)
OUTS
Outside Temperature (logged in SH types only)
Deg C
-
-
S5 (C54)
FLSP
Primary Temperature Setpoint
Deg C
-
-
S6 (C55)
BLOP
Boiler Output
%
-
-
S7 (C56)
VTPN
VT Valve Position
%
-
-
S8 (C57)
ZDMD
Maximum Zone Demand
%
-
-
S9 (C58)
VTSP
VT Setpoint
Deg C
-
-
K1 (C60)
MAXF
Maximum Primary Setpoint
Deg C
80
0 to 100
K2 (C61)
MINR
Minimum Return Setpoint
Deg C
40
0 to 100
   

Engineering Parameters; only accessible via Doorway and InSite

     
C83
MANL
Used with W5 HAND to position VT Valve manually
%
0
0 to 100
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
GENA
General Alarm input ‘a’ (when set to 1)
-
-
0 or 1
C92
GENB
General Alarm input ‘b’ (when set to 1)
-
-
0 or 1
C93
LOKA
Lockout Alarm Boiler 1 (when set to 1)
-
-
0 or 1
C94
LOKB
Lockout Alarm Boiler 2 (when set to 1)
-
-
0 or 1
C95
FREZ
Danger of freezing (when set to 1)
-
 
0 or 1
C96
STOP
STOP alarm (when set to 1)
-
-
0 or 1
C97
OUTF
Outside temperature failed (when set to 1)
-
-
0 or 1
C98
FROS
Frost protection stage 3 in progress (when set to 1)
-
-
0 or 1
C99
PMPF
Pump Failure (PCO Submodule)
-
-
0 or 1
C150
MNVO
Minimum Variable Output :sets lowest level to run modulating Boilers
%
20
0 to 100
C151
MXPL
Run Maximum number of Condensing Boilers in Parallel
-
0
0 to 1
    * 24 hour plots available for these values by default      
    Plotting interval and plotted variable changeable via Doorway or InSite      