30 July 1996
Software
release notes
Boiler Controller BV2q (BD2q)
Unless specifically excluded all features apply to both versions.
- Improve update rate on MaxTrim output to keep
in sync with the zone which is demanding most heat.
- Correct the default number of boiler config
variables displayed on a zone controller to include MODE, the default is for MODE =1.
- Speed up detection of missing nodes. On a 100
zone system the maximum time needed to detect a missing or failed node is 3 minutes.
- Registration support added for
- 100 zones
- 8 SLT's
- 20 Heat sources (CT and VT controllers)
- 20 Cooling sources (CT and VT controllers)
- 4 Boiler Cascades
- 3 boiler Pump Changeover
- 1 Active outside air sensor
- VT version only, output driver
types added to provide different sequence types.
- TYPE 1 boiler sequence (max 8 boilers) with
automatic boiler rotation, longest off-first on, longest on-first off.
- TYPE 2 High/Low burner control on up to 4
boilers. The four boilers are sequenced with the longest off-first on, longest on-first
off stratagy.
- TYPE 3 Fixed boiler sequence (max 8 boilers)
with fixed lead
- Boiler cascade module
support added, the state of the cascade module 'boiler disable' or 'boiler lockout' signal
is read and the effected boiler removed from the sequence. The boiler is automatically
reinstated when the condition is cleared.
- New config variable 'all
remote' AREM added. When set to 1 this causes the Boiler controller to sequence only those
boilers connected using cascade boiler controllers, thus 'lockout' monitoring can be used
on all boilers.
- When cascade modules are
registered with a boiler controller the 'number of boilers' is incremented to take account
of the new boilers connected. If an odd number of boilers are in use the config variable
BLRS needs to be changed to reflect this.
- read only config variable has been added, BLOK
'boilers OK' this reports how many boilers are available for use by the sequencer.
- Support for Pump Changeover(PCO) modules added.
The boiler controller can have up to 3 Pump Changeover modules registered with it, the TYPE
config variable in the PCO module needs to be set up to define the function of the
pump under control. The types are mapped for the two boiler controller versions as follows
PCO TYPE
|
BLR-VT
|
BLR-DHW
|
1
|
primary pump
|
primary pump
|
2
|
VT pump
|
heating relay
|
3
|
|
DHW relay
|