Boiler Controller
with VT Circuit (STD) and Hi/Lo Fired with VT Circuit (HIL)

Notes
(STD)
Notes
(HIL)
Configuration Tables Data Sheet B1 (STD)
(1120kb PDF) s/w version 4c1
Data Sheet B2 (HIL)
(989kb PDF) s/w version 4c1
Wiring
(STD)
Wiring
(HIL)
History

Configuration Tables

Latest released version is 4c2
Document last updated 01/11/2001
Recent features not included on Data sheet are in
RED text

Configuration Parameters

Doorway / InSite Code Label Description Units Default Value Range
C1 FRST Frost Protection / Non Occupied Setpoint Deg C 3 2 to 15
C2 MAXF Maximum Primary Setpoint Deg C 80 30 to 110
C3 MINR Minimum Return Setpoint Deg C 40 10 to 50
C4 FLAV Flow Temperature for 10°C outside temperature Deg C 50 20 to 100
C5 SACT Sensor Action
0: Use flow or return, or average if both sensors valid
1: Use flow sensor value
2: Use return sensor value
3: Use average of flow and return sensor values
- 1 0 to 3
C6 BLRS Number of boilers in sequence - 2 1 to 8
C7 MXVT Maximum VT circuit water temperature Deg C 80 20 to 100
C8 VLIM

Limits the opening of VT valve if return temp is below MINR
0%: Valve will close fully if Return > 10 Deg C below MINR
50%: Valve will close 50% if Return > 10 Deg C below MINR
100%: Valve will control normally, no limitation

% 100 0 to 100
C9 DHWP Hot Water Priority:
0: Hot water and heating have equal priority
1: VT valve closes when DHW is demanding heat
- 0 0 to 1
C10 MIN Boiler minimum run time Mins 5 1 to 20
C11 BRON

Primary pump run on time

Mins 5 0 to 30
C12 PERD VT valve stroke time Secs/10 18 2 to 60
C13 TRNG Maximum trim effect on heating setpoint Deg C 10 0 to 20
C14 CRNG Maximum adaptive effect on heating setpoint Deg C 10 0 to 20
C15 MODE Mode select:
0: VT Valve held shut while Primary Pump only runs on
Actuator demands match zone heat demand
1: VT Valve opened while Primary and VT Pumps run on
Actuator demands match zone heat demand
2: VT Valve opened while Primary and VT Pumps run on
All actuators opened proportional to highest zone demand
Note in non-Housekeeping Boiler Controllers this parameter is fixed MODE=0.
- 0 0 to 2
C16 BLOK Number of boiler stages available to run (i.e. not locked out) - read only 0 to 8
C17 AREM

All boilers remote
0: Boiler outputs on controller included in sequence
1: All boiler stages via cascade modules
Boiler Controller outputs disabled

- 0 0 to 1
C18 SMRT

Summer heating inhibit if outside temperature > SMRT

Deg C 20 10 to 30
C19 MIND Minimum Demand for Boiler Controller to operate
0: When demand drops to zero, boilers and pumps continue to run
MIND > 1: When demand drops to zero, boilers and pumps stop
% 2 0 to 10
C20 COMP Compensator offset Deg C 0 -50 to 50
C21 ALRM Alarm Mode
0: Ignore alarms
1: Disable Boiler outputs, no alarm (maintenance switches)
2: Report all alarms, continue running (lockout alarms)
3: Report all alarms, continue running (general alarms)
4: Report all alarms, shut down on STOP alarm only
5: Report all alarms, shut down on STOP alarm or “Master Off”
- 0 0 to 5
C22 ALST Alarm report sense
0: Alarm if input = 0 (contact open)
1: Alarm if input = 1 (contact closed)
- 1 0 to 1
C23 DOMN Own Domain (for SH types only) - 0 0 to 8
C24 TYPE Output type : Not available from Zone Controller (Doorway only). Factory set to:
1 = Normal sequencing of stages
3 = Fixed sequencing of stages
- 1 0 to 3
C25 MNVF Minimum VT Flow: used to ensure a minimum opening on the VT valve while the boilers are running. This only needs to be used when the Boiler does not have a pumped primary circuit or shunt circuit. % 0 0 to 100

 

Monitoring Parameters

Doorway / InSite Code Label Description Units Default Value Range
I1 (C30) INPA External input ‘a’ status - - 0 to 1
I2 (C31) INPB External input ‘b’ status - - 0 to 1
I3 (C32) BLRA Boiler 1 output status - - 0 to 1
I4 (C33) BLRB Boiler 2 output status - - 0 to 1
I5 (C34) PPMP Primary pump output status - - 0 to 1
I6 (C35) VTOP VT valve open output status - - 0 to 1
I7 (C36) VTCL VT valve close output status - - 0 to 1
I8 (C37) VPMP Secondary pump output status - - 0 to 1
W1 (C38) AUTO Automatic/Manual Status - - 0 to 1
W2 (C39) OVRD Override - - 0 to 1
W3 (C40) SHOF Summer heating (inhibited if SHOF = 1) - read only 0 to 1
W4 (C41) ZBST Zone boost (disabled if ZBST = 0) - 1 0 to 1
W5 (C42) HAND Manual HAND mode - 0 0 to 1
W6 (C43) RPLN Replace missing nodes in Database (for SH types only) - 1 0 to 1
W7 (C44) SERV Service Pin Msg (to Doorway +InSite, self resetting) - - 0 to 1
W8 (C45) CGST Configuration Mode Status - - 0 to 1
S1* (C50) FLOW Flow Temperature Deg C - -
S2* (C51) RTRN Return Temperature Deg C - -
S3* (C52) VTMP VT circuit Temperature Deg C - -
S4* (C53) OUTS Outside Temperature (logged in SH types only) Deg C - -
S5 (C54) FLSP Primary Temperature Setpoint Deg C - -
S6 (C55) BLOP Boiler Output % - -
S7 (C56) VTPN VT Valve Position % - -
S8 (C57) ZDMD Maximum Zone Demand % - -
S9 (C58) VTSP VT Setpoint Deg C - -
K1 (C60) MAXF Maximum Primary Setpoint Deg C 80 0 to 100
K2 (C61) MINR Minimum Return Setpoint Deg C 40 0 to 100
    Engineering Parameters; only accessible via Doorway and InSite      
C83 MANL Used with W5 HAND to position VT Valve manually
% 0 0 to 100
C90 NOAL No Alarms; all alarms cleared when set to 1 - - 0 or 1
C91 GENA General Alarm input ‘a’ (when set to 1) - - 0 or 1
C92 GENB General Alarm input ‘b’ (when set to 1) - - 0 or 1
C93 LOKA Lockout Alarm Boiler 1 (when set to 1) - - 0 or 1
C94 LOKB Lockout Alarm Boiler 2 (when set to 1) - - 0 or 1
C95 FREZ Danger of freezing (when set to 1) -   0 or 1
C96 STOP STOP alarm (when set to 1) - - 0 or 1
C97 OUTF Outside temperature failed (when set to 1) - - 0 or 1
C98 FROS Frost protection stage 3 in progress (when set to 1) - - 0 or 1
C99 PMPF Pump Failure (PCO Submodule) - - 0 or 1
    * 24 hour plots available for these values by default      