Feature Notes
|
Boiler Controller
|
Latest released version is 4d1
|
BLR / DIN / STD/ ...BLR / DIN / HIL/ ... |
Main FeaturesControls 2 Boilers and associated plantUp to 8 Boilers in one sequence using Boiler Cascade SubmodulesSelf adapting Weather CompensationSystem Housekeeping function optionBoiler plant operates on demand from the building, not fixed time programmeAutomatic sequencing of Modulating Boilers efficient control of condensing boilers
|
![]() |
Input 9-10 |
Flow Sensor |
Input 11-12 |
Return Sensor |
Input 13-14 |
VT Sensor |
Input 15-16 |
Outside Sensor |
SACT = 0 |
Control on flow or return or average if both sensors valid |
SACT = 1 |
Control on Flow sensor only |
SACT = 2 |
Control on Return sensor only |
SACT = 3 |
Control on average of Flow and Return sensor values |
CRNG = 0 |
Disables Zone Trim and Adaption. |
TRNG = 0 |
Disables Zone Trim and Adaption. |
ZBST = 0 |
Disables Boost Mode. |
MIND = 0 |
Ensures VT pumps run constantly during occupancy. |
Boiler Class |
starting order/ increasing demand |
stopping order/decreasing demand |
condensing and modulating |
1 |
4 |
condensing |
2 |
3 |
modulating |
3 |
2 |
fixed fire |
4 |
1 |
MODE = 0 |
Primary Pumps run for BRON period. |
MODE = 1 |
Primary and VT Pumps run on and VT Valve open for BRON period. |
MODE = 2 |
Primary and VT Pumps run on and VT Valve open and Zone valves overridden
to 100% for BRON period. |
NOAL |
No Alarms.
|
GENA |
General Alarm on VFC input a |
GENB |
General Alarm on VFC input b |
LOKA |
Lockout Alarm on VFC input a |
LOKB |
Lockout Alarm on VFC input b |
FREZ |
Danger of Freezing alarm. |
STOP |
System STOP alarm generated.
|
OUTF |
Outside temperature Fail alarm. |
FROS |
Frost protection in progress. |
PMPF |
Pump Fail |
Status Monitoring Only |
The status of inputs can be read on parameters |
Boiler Stage Shutdown, no Alarms |
Often used for Maintenance switches, or |
Boiler Lockout Alarm |
Used for Lockout signals |
Boiler General Alarm |
Used for General alarm signals
|
General Plant Shutdown, Stop Alarm |
Used for external critical alarms |
Boiler Shutdown, or Master Off Alarm |
Used for external critical alarms |
Input 5-6 |
VFC input a |
Input 7-8 |
VFC input b |
ALRM = 0 |
Inputs used for monitoring only |
ALRM = 1 |
Inputs used for maintenance |
ALRM = 2 |
Inputs used for Lockout alarms |
ALRM = 3 |
Inputs used for General alarms |
ALRM = 4 |
Inputs used for STOP alarm |
ALRM = 5 |
Inputs used for STOP or Master Off |
H |
Heat Source |
20 |
C |
Cool Source |
20 |
A |
AHU Controller |
50 |
Z |
Zones |
100 |
M |
Monitoring Modules |
25 |
S |
Communications |
4 |
R |
Routers |
4 |
Option |
Function |
Max Cascade Submodules |
Max PCO Submodules |
/ SH / 001 |
With duty and sequence rotation, with housekeeping |
4 |
3 |
/ SH / 003 |
With fixed sequence, with housekeeping |
4 |
3 |
/ NH / 004 |
With duty and sequence rotation, no housekeeping |
2 |
1 |
/ NH / 006 |
With fixed sequence, no housekeeping |
2 |
1 |