Boiler Controller

with VT Circuit (STD) and Hi/Lo Fired with VT Circuit (HIL)

Notes
(STD)
Notes
(HIL)
Configuration Tables Data Sheet (STD)
Data Sheet (HIL)
Wiring
(STD)
Wiring
(HIL)
History

Configuration Tables

Latest released version is 4c4

Document last updated 06/07/02
Recent features not included on Data sheet are in
RED text

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
FRST
Frost Protection / Non Occupied Setpoint
Deg C
3
2 to 15
C2
MAXF
Maximum Primary Setpoint
Deg C
80
30 to 110
C3
MINR
Minimum Return Setpoint
Deg C
40
10 to 50
C4
FLAV
Flow Temperature for 10°C outside temperature
Deg C
50
20 to 100
C5
SACT
Sensor Action
0: Use flow or return, or average if both sensors valid
1: Use flow sensor value
2: Use return sensor value
3: Use average of flow and return sensor values
-
1
0 to 3
C6
BLRS
Number of boilers in sequence
-
2
1 to 8
C7
MXVT
Maximum VT circuit water temperature
Deg C
80
20 to 100
C8
VLIM
Limits the opening of VT valve if return temp is below MINR
0%: Valve will close fully if Return > 10 Deg C below MINR
50%: Valve will close 50% if Return > 10 Deg C below MINR
100%: Valve will control normally, no limitation
%
100
0 to 100
C9
DHWP
Hot Water Priority:
0: Hot water and heating have equal priority
1: VT valve closes when DHW is demanding heat
-
0
0 to 1
C10
MIN
Boiler minimum run time
Mins
5
1 to 20
C11
BRON
Primary pump run on time
Mins
5
0 to 30
C12
PERD
VT valve stroke time
Secs/10
18
2 to 60
C13
TRNG
Maximum trim effect on heating setpoint
Deg C
10
0 to 20
C14
CRNG
Maximum adaptive effect on heating setpoint
Deg C
10
0 to 20
C15
MODE
Mode select:
0: VT Valve held shut while Primary Pump only runs on
Actuator demands match zone heat demand
1: VT Valve opened while Primary and VT Pumps run on
Actuator demands match zone heat demand
2: VT Valve opened while Primary and VT Pumps run on
All actuators opened proportional to highest zone demand
Note in non-Housekeeping Boiler Controllers this parameter is fixed MODE=0.
-
0
0 to 2
C16
BLOK
Number of boiler stages available to run (i.e. not locked out)
-
read only
0 to 8
C17
AREM
All boilers remote
0: Boiler outputs on controller included in sequence
1: All boiler stages via cascade modules
Boiler Controller outputs disabled
-
0
0 to 1
C18
SMRT
Summer heating inhibit if outside temperature > SMRT
Deg C
20
10 to 30
C19
MIND
Minimum Demand for Boiler Controller to operate
0: When demand drops to zero, boilers and pumps continue to run
MIND > 1: When demand drops to zero, boilers and pumps stop
%
2
0 to 10
C20
COMP
Compensator offset
Deg C
0
-50 to 50
C21
ALRM
Alarm Mode
0: Ignore alarms
1: Disable Boiler outputs, no alarm (maintenance switches)
2: Report all alarms, continue running (lockout alarms)
3: Report all alarms, continue running (general alarms)
4: Report all alarms, shut down on STOP alarm only
5: Report all alarms, shut down on STOP alarm or “Master Off”
-
0
0 to 5
C22
ALST
Alarm report sense
0: Alarm if input = 0 (contact open)
1: Alarm if input = 1 (contact closed)
-
1
0 to 1
C23
DOMN
Own Domain (for SH types only)
-
0
0 to 8
C24
TYPE
Output type : Not available from Zone Controller (Doorway only). Factory set to:
1 = Normal sequencing of stages
3 = Fixed sequencing of stages
-
1
0 to 3
C25
MNVF
Minimum VT Flow: used to ensure a minimum opening on the VT valve while the boilers are running. This only needs to be used when the Boiler does not have a pumped primary circuit or shunt circuit.
%
0
0 to 100

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
INPA
External input ‘a’ status
-
-
0 to 1
I2 (C31)
INPB
External input ‘b’ status
-
-
0 to 1
I3 (C32)
BLRA
Boiler 1 output status
-
-
0 to 1
I4 (C33)
BLRB
Boiler 2 output status
-
-
0 to 1
I5 (C34)
PPMP
Primary pump output status
-
-
0 to 1
I6 (C35)
VTOP
VT valve open output status
-
-
0 to 1
I7 (C36)
VTCL
VT valve close output status
-
-
0 to 1
I8 (C37)
VPMP
Secondary pump output status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
SHOF
Summer heating (inhibited if SHOF = 1)
-
read only
0 to 1
W4 (C41)
ZBST
Zone boost (disabled if ZBST = 0)
-
1
0 to 1
W5 (C42)
HAND
Manual HAND mode
-
0
0 to 1
W6 (C43)
RPLN
Replace missing nodes in Database (for SH types only)
-
1
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
FLOW
Flow Temperature
Deg C
-
-
S2* (C51)
RTRN
Return Temperature
Deg C
-
-
S3* (C52)
VTMP
VT circuit Temperature
Deg C
-
-
S4* (C53)
OUTS
Outside Temperature (logged in SH types only)
Deg C
-
-
S5 (C54)
FLSP
Primary Temperature Setpoint
Deg C
-
-
S6 (C55)
BLOP
Boiler Output
%
-
-
S7 (C56)
VTPN
VT Valve Position
%
-
-
S8 (C57)
ZDMD
Maximum Zone Demand
%
-
-
S9 (C58)
VTSP
VT Setpoint
Deg C
-
-
K1 (C60)
MAXF
Maximum Primary Setpoint
Deg C
80
0 to 100
K2 (C61)
MINR
Minimum Return Setpoint
Deg C
40
0 to 100
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C83
MANL
Used with W5 HAND to position VT Valve manually
%
0
0 to 100
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
GENA
General Alarm input ‘a’ (when set to 1)
-
-
0 or 1
C92
GENB
General Alarm input ‘b’ (when set to 1)
-
-
0 or 1
C93
LOKA
Lockout Alarm Boiler 1 (when set to 1)
-
-
0 or 1
C94
LOKB
Lockout Alarm Boiler 2 (when set to 1)
-
-
0 or 1
C95
FREZ
Danger of freezing (when set to 1)
-
 
0 or 1
C96
STOP
STOP alarm (when set to 1)
-
-
0 or 1
C97
OUTF
Outside temperature failed (when set to 1)
-
-
0 or 1
C98
FROS
Frost protection stage 3 in progress (when set to 1)
-
-
0 or 1
C99
PMPF
Pump Failure (PCO Submodule)
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 