Description |
Units |
Default Value |
Range |
C1 |
FRST |
Frost Protection / Non Occupied Setpoint |
Deg C |
3 |
2 to 15 |
C2 |
MAXF |
Maximum Primary Setpoint |
Deg C |
80 |
30 to 110 |
C3 |
MINR |
Minimum Return Setpoint |
Deg C |
40 |
10 to 50 |
C4 |
FLAV |
Flow Temperature for 10°C outside temperature |
Deg C |
50 |
20 to 100 |
C5 |
SACT |
Sensor Action |
- |
1 |
0 to 3 |
C6 |
BLRS |
Number of boilers in sequence |
- |
2 |
1 to 8 |
C7 |
MXVT |
Maximum VT circuit water temperature |
Deg C |
80 |
20 to 100 |
C8 |
VLIM |
Limits the opening of VT valve if return temp is below MINR |
% |
100 |
0 to 100 |
C9 |
DHWP |
Hot Water Priority: |
- |
0 |
0 to 1 |
C10 |
MIN |
Boiler minimum run time |
Mins |
5 |
1 to 20 |
C11 |
BRON |
Primary pump run on time |
Mins |
5 |
0 to 30 |
C12 |
PERD |
VT valve stroke time |
Secs/10 |
18 |
2 to 60 |
C13 |
TRNG |
Maximum trim effect on heating setpoint |
Deg C |
10 |
0 to 20 |
C14 |
CRNG |
Maximum adaptive effect on heating setpoint |
Deg C |
10 |
0 to 20 |
C15 |
MODE |
Mode select:
|
- |
0 |
0 to 2 |
C16 |
BLOK |
Number of boiler stages available to run (i.e. not locked out) |
- |
read only |
0 to 8 |
C17 |
AREM |
All boilers remote |
- |
0 |
0 to 1 |
C18 |
SMRT |
Summer heating inhibit if outside temperature > SMRT |
Deg C |
20 |
10 to 30 |
C19 |
MIND |
Minimum Demand for Boiler Controller to operate |
% |
2 |
0 to 10 |
C20 |
COMP |
Compensator offset |
Deg C |
0 |
-50 to 50 |
C21 |
ALRM |
Alarm Mode |
- |
0 |
0 to 5 |
C22 |
ALST |
Alarm report sense |
- |
1 |
0 to 1 |
C23 |
DOMN |
Own Domain (for SH types only) |
- |
0 |
0 to 8 |
C24 |
TYPE |
Output type : Not available from Zone Controller (Doorway
only). Factory set to: |
- |
1 |
0 to 3 |
C25 |
MNVF |
Minimum VT Flow: used to ensure a minimum opening on the VT valve while the boilers are running. This only needs to be used when the Boiler does not have a pumped primary circuit or shunt circuit. |
% |
0 |
0 to 100 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
INPA |
External input a status |
- |
- |
0 to 1 |
I2 (C31) |
INPB |
External input b status |
- |
- |
0 to 1 |
I3 (C32) |
BLRA |
Boiler 1 output status |
- |
- |
0 to 1 |
I4 (C33) |
BLRB |
Boiler 2 output status |
- |
- |
0 to 1 |
I5 (C34) |
PPMP |
Primary pump output status |
- |
- |
0 to 1 |
I6 (C35) |
VTOP |
VT valve open output status |
- |
- |
0 to 1 |
I7 (C36) |
VTCL |
VT valve close output status |
- |
- |
0 to 1 |
I8 (C37) |
VPMP |
Secondary pump output status |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
SHOF |
Summer heating (inhibited if SHOF = 1) |
- |
read only |
0 to 1 |
W4 (C41) |
ZBST |
Zone boost (disabled if ZBST = 0) |
- |
1 |
0 to 1 |
W5 (C42) |
HAND |
Manual HAND mode |
- |
0 |
0 to 1 |
W6 (C43) |
RPLN |
Replace missing nodes in Database (for SH types only) |
- |
1 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
S1* (C50) |
FLOW |
Flow Temperature |
Deg C |
- |
- |
S2* (C51) |
RTRN |
Return Temperature |
Deg C |
- |
- |
S3* (C52) |
VTMP |
VT circuit Temperature |
Deg C |
- |
- |
S4* (C53) |
OUTS |
Outside Temperature (logged in SH types only) |
Deg C |
- |
- |
S5 (C54) |
FLSP |
Primary Temperature Setpoint |
Deg C |
- |
- |
S6 (C55) |
BLOP |
Boiler Output |
% |
- |
- |
S7 (C56) |
VTPN |
VT Valve Position |
% |
- |
- |
S8 (C57) |
ZDMD |
Maximum Zone Demand |
% |
- |
- |
S9 (C58) |
VTSP |
VT Setpoint |
Deg C |
- |
- |
K1 (C60) |
MAXF |
Maximum Primary Setpoint |
Deg C |
80 |
0 to 100 |
K2 (C61) |
MINR |
Minimum Return Setpoint |
Deg C |
40 |
0 to 100 |
Engineering Parameters; only accessible via Doorway and InSite |
|||||
C83 |
MANL |
Used with W5 HAND to position VT Valve manually |
% |
0 |
0 to 100 |
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
GENA |
General Alarm input a (when set to 1) |
- |
- |
0 or 1 |
C92 |
GENB |
General Alarm input b (when set to 1) |
- |
- |
0 or 1 |
C93 |
LOKA |
Lockout Alarm Boiler 1 (when set to 1) |
- |
- |
0 or 1 |
C94 |
LOKB |
Lockout Alarm Boiler 2 (when set to 1) |
- |
- |
0 or 1 |
C95 |
FREZ |
Danger of freezing (when set to 1) |
- |
0 or 1 |
|
C96 |
STOP |
STOP alarm (when set to 1) |
- |
- |
0 or 1 |
C97 |
OUTF |
Outside temperature failed (when set to 1) |
- |
- |
0 or 1 |
C98 |
FROS |
Frost protection stage 3 in progress (when set to 1) |
- |
- |
0 or 1 |
C99 |
PMPF |
Pump Failure (PCO Submodule) |
- |
- |
0 or 1 |