History
|
Fan Coil Controller
|
|
FCU / DIN / 7R / [driver option] |
PROM file header: FCUF
Software Version | Release Date | Additional Information | Notes |
4d6 | 17/11/05 |
change operation of supply temperature control at low heating demands (less than 5%) to maintain minimum supply temperature so long as unit is in occupation and the fan is running. Previously the heating and cooling batteries were shut down for demands below 5%. |
|
4d5 | 18/10/05 |
add Maintain Off as a new feature. Allows an Override to off to be maintained
until cancelled, mainly used in residential applications to disable A/C. |
|
4d3 | 17/03/05 |
pass FanSpeed demands onto slave FanCoils so that Knob or Helvar switches can be used to control the fan speed across a group of FanCoils correct Fan Speed control from Helvar switch, fault introduced at 4d2 No config changes |
|
4d2 | 05/02/05 |
allow registered actuators to receive FanSpeed demands No feature or config changes |
|
4d1 | 05/09/03 | add FanSpeed to knobs -1 sets Auto add overide to ON if Fan Speed set on Knob set 0 to stop unit add speed selection from LSW switches |
|
4c5 | 06/12/02 | change demands sent to registered actuators when MIDP<0. Send the same demands as for the internal drivers rather than sending the supply loop demands. This allows two pipe applications to extend the internal drivers by using actuator controllers. | |
4c4 | not released | ||
4c3 |
15/11/00 |
0023/0001 C3 | add driver rescaling for use in slave FCU applications |
4c2 | 02/05/00 | 0023/0001 C3 | improve flashing of HTSC, CLSC, OCDS and slave links |
4c1 |
15/02/00 |
0023/0001 C3 |
major new issue |
4b7 | 18/08/99 | 0023/0001 C3 | add automatic sensor calibration |
4b6 | 03/08/99 | 0023/0001 C3 |
remove automatic entry into TEST mode on prom change extend test inputs to include all inputs |
4b5 |
23/07/99 |
0023/0001 C3 |
add HTCT, CLCT support, allows sending of CT setpoint to Boilers and Secondary boilers remove MXCT, MNCT |
4b4 | 20/07/99 | 0023/0001 C3 | correct fan switch inf fault introduced in version 4b3 |
4b3 |
16/07/99 |
0023/0001 C3 |
correct sending of demands to 1 per minute add capability for different maximum speeds in heating and cooling improve universal driver now version 4a |
4b2 |
21/04/99 |
0023/0001 C3 |
change specification of Trim Pot to match Sontay standard product add support for Sontay Fan Switch |
4b1 |
08/04/99 |
0023/0001 C3 |
add support for EXTERNAL_BINDING as special build option add support for PIR sensor in EXT version add production test mode |
4a3 | 01/03/99
|
0023/0001 A |
upgrade to dual domain add support for OPEN network variables add occupaction override from Doorway add HAND control of outputs from Doorway |
3d1 |
08/07/98 |
0023/0001 A |
add airside damper control
|
3c5 | 06/07/98 | 0023/0001 A |
correct registration error when using SPTY 2 correct manual operation when no sensor fitted |
3c4 | 02/06/98 | 0023/0001 A |
add support for nviHeatTrim and nviCoolTrim to refresh no comms timer add remote control of 'registration button' switch 7 add count of non power up resets C85 SWRS count of no comms reset renamed C84 NCRS |
3c3 | 22/05/98 | 0023/0001 A |
add reset if no comms received for 10 minutes add registration of ACT and PCO modules |
3c2 | 09/03/98 | 0023/0001 A | correct manual mode and driver setup |
3c1 |
20/01/98 |
0023/0001 A | first issue |