FCU Configuration variables

ref
 
Description
default
range
C1
SPFC
Occupied Setpoint
20
10.0 to 35.0C
C2
SPDB
Setpoint Deadband
1.0
0.0 to 10.0C
C3
SPTR
Setpoint Trim
0
-10.0 to 10.0 C
C4
SPTY
Setpoint Type, control mode
0 control to SPFC, occupation from Master Zone
1 SPFC supervised from Master Zone
2 Off Coil temperature control, Heat/Cool demands from Zone Controller or another Fan Coil
1
0 to 2
C5
INMD
Input Mode use of terminals 'temp'
0 supply temperature
1 window contact (short = occupied) AND internal occ
2 Time Clock OR internal clock
3 External occupation signal only
4 Alarm input
 
0
0 to 4
C6
MAXH
Maximum Supply Heating setpoint
30
0 to 90C
C7
MINH
Minimum Supply Heating setpoint
20
0 to 90C
C8
MAXC
Maximum Supply Cooling setpoint
18
2 to 30C
C9
MINC
Minimum Supply Heating setpoint
10
2 to 30C
C10
MIND
Supply minimum demand, used for switching between heating and cooling
4
0.0 to 10.0
C11
OCCO
When set controller will only run during the occupied period 
0
0 to 1
C12
HPRD
heating valve period or minimum on time
depends on driver type
1 to 60 secs/10
C13
HDLY
Interlock delay
negative value delays fan (or pump) after heating starts
positive value cause run on of fan after heating shuts down
0
-30.0 to 30.0 minutes
C14
CPRD
cooling valve period or minimum on time
depends on driver type
1 to 60 secs/10
C15
CDLY
Interlock delay
negative value delays fan (or pump) after cooling starts
positive value cause run on of fan after cooling shuts down
0
-30.0 to 30.0 minutes
C16
FPRD
Fan period, minimum time to change fan speed steps
12 (2 minutes)
1 to 60 secs/10
C17
FRPT
Frost protect
0 no action
1 open heating valve 50%
2 open heating valve and run pump/fan
0
0 to 2
C18
MANL
Manual level , from Doorway
0
-100 to 100 %
C19 
HTSC
Heat source
1
-1 to 100
C20
CLSC
Cool source
0
-1 to 100
C21
MXCT
Maximum CT setpoint
70
20 to100 C
C22
MNCT
Minimum CT setpoint
50
20 to 100 C
C23
ALRM
 alarm mode  
0 ignore alarms
1 report alarms
2 report alarms, shut down all outputs on alarm
3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm
1
0 to 3
C24
ALST
not used 
0
0 to 1
C25
MXVA*
Maximum voltage channel A
10.0
0.0 to 10.0 volt
C26
MNVA*
Minimum voltage channel A
0.0
0.0 to 10.0 volt
C27
MXVB*
Maximum voltage channel B
10.0
0.0 to 10.0 volt
C28
MNVB*
Minimum voltage channel B
0.0
0.0 to 10.0 volt


*AOP versions only

Digital monitoring
6R derivatives (Boiler Board)

ref
 
Description
default
range
C30
INPA
input A  occupation/window contact et al
 
0 to 1
C31
INPB
input B
 
0 to 1
C32
RLYA
relay A
 
0 to 1
C33
RLYB
relay B
 
0 to 1
C34
RLYC
relay C
 
0 to 1
C35
RLYD
relay D (fan A)
 
0 to 1
C36
RLYE
relay E (fan B)
 
0 to 1
C37
RLYF
relay F (fan C)
 
0 to 1
C38
AUTO
Automatic/manual mode
 
0 to 1
C39
OVRD
override
 
0 to 1
C45
CGST
configuration mode
   


other boards

ref
 
Description
default
range
C30
INPA
input A  occupation/window contact et al
 
0 to 1
C31
OCCD
occupied
 
0 to 1
C32
 
not used
 
0 to 1
C33
 
not used
 
0 to 1
C34
COOL
cooling mode
 
0 to 1
C35
RLYA
relay A
 
0 to 1
C36
RLYB
relay B
 
0 to 1
C37
RLYC
relay C
 
0 to 1
C38
AUTO
Automatic/manual mode
 
0 to 1
C39
OVRD
override
 
0 to 1
C45
CGST
configuration mode
   


sensors

ref
 
Description
default
range
C50
SPLA
supply air temperature
 
5.0 to 35.0 C 
C51
RTNA
return air temperature
 
5.0 to 35.0 C
C52
HCOP
heat cool output to drivers (cooling negative)
 
-100 to 100 %
C53
SPSL
supply (off coil) setpoint
 
5.0 to 35.0 C
C54
SPRT
return air setpoint
 
5.0 to 35.0 C
C55
HDMD
heat demand from return loop or from Zone Controller
 
0 to 100%
C56
CDMD
cool demand from return loop or from Zone Controller
 
0 to 100%


knobs

ref
 
Description
default
range
C60
SPOC
Occupied setpoint
20.0
5.0 to 35.0 C
C61
SPNO
Non Occupied setpoint
10.0
5.0 to 20.0 C
C62
SPSV
Supervised setpoint from Master controller
 
0 to 35.0 C
C63
SPTR
Setpoint Trim
0
-10.0 to 10.0 C 


loop parameters

ref
 
Description
default
range
C69
RTLP
selects Return Loop parameters
0
0 to 1
C70
UNDH
sets very Low muzzy level for heating loop
3.5 :1.00
10 to 200
C71
OVRH
sets very High muzzy level for heating loop
3.5 :1.00
10 to 200
C72
DBBH
deadband sets limit for OK band for heating loop
1.5 :0.50
10 to 100
C73
RCGH
max rate of change heating
 
5 to 100
C74
GN H
gain heating
20 :50
1 to 200
C75
UNDC
sets very Low muzzy level for cooling loop
3.5 :1.00
10 to 200
C76
OVRC
sets very High muzzy level for cooling loop
3.5 :1.00
10 to 200
C77
DBBC
deadband sets limit for OK band for cooling loop
1.5 :0.50
10 to 100
C78
RCGC
max rate of change cooling
 
5 to 100
C79
GN C
gain cooling
20 :50
1 to 200


System

ref
 
Description
default
range
C80
XCFG 
forces exit from config mode
   
C81
 GRP
own group number
   


Alarms

ref
 
Description
default
range
C90
NOAL 
no alarm
   
C91
SENF
sensor fail
   
C92
EXTN
alarm for external input
   
C93
STOP
STOP alarm received
   




Registration table

ref
 
Description
default
range
C100
#ACT
number of Actuators registered to this controller
   
         


Documentation

ref
 
Description
default
range
C120
SLVE
denotes that this is a Slave Fan Coil
0
0 to 1
C121
MZON
zone number of master zone
0
0 to 200


Plot configuration

ref
 
Description
default
range
C130
PN A
 config variable number for channel A 
51
0 to 255
C131
PT A
period code for plot A
1
1 to 4
C132
PN B
 config variable number for channel B 
52
0 to 255
C133
PT B
period code for plot B
1
1 to 4
C134
PN C
 config variable number for channel C 
53
0 to 255
C135
PT C
period code for plot C
1
1 to 4


Driver Parameter

ref
 
Description
default
range
C150
HTYP
heating driver type
 
0 to 5
C151 
HSTG
number of heating stages
 
0 to 8
C152
CTYP
cooling driver type
 
0 to 5
C153 
CSTG
number of cooling stages
 
0 to 8
C154
FTYP
fan driver type
 
0 to 7
C155 
FSTG
number of fan stages
 
0 to 5