Configuration Tables
|
Fan Coil Controller
|
issue 4d1-4d3
|
FCU / DIN / ... |
Configuration Parameters |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SPFC |
Occupied Return temperature Setpoint |
Deg C |
20 |
10 to 35 |
C2 |
SPDB |
Setpoint Deadband |
Deg C |
1 |
0 to 10 |
C3 |
SPTR |
Setpoint Trim |
Deg C |
0 |
-10 to 10 |
C4 |
SPTY |
Setpoint type
|
Deg C |
1 |
0 to 2 |
C5 |
INMD |
Input mode for terminals temp a ( 'input a' for 7R )
|
- |
0 |
0 to 4 |
C6 |
MAXH |
Supply maximum heating setpoint |
Deg C |
30 |
0 to 90 |
C7 |
MINH |
Supply minimum heating setpoint |
Deg C |
20 |
0 to 90 |
C8 |
MAXC |
Supply maximum cooling setpoint |
Deg C |
18 |
2 to 30 |
C9 |
MINC |
Supply minimum cooling setpoint |
Deg C |
10 |
2 to 30 |
C10 |
MIND |
Supply minimum demand, used for switching between heating and cooling
|
- |
4 |
0 to 10 |
C11 |
OCCO |
When set, controller will only run during the Occupied Period |
- |
0 |
0 to 1 |
C12 |
HPRD |
Heating valve period or minimum time |
Secs/10 |
6 |
0 to 60 |
C13 |
HDLY |
Heating interlock delay. Negative value delays fan (or pump)
|
Mins |
0 |
-30 to 30 |
C14 |
CPRD |
Cooling Valve period or minimum On time |
Secs/10 |
6 |
1 to 60 |
C15 |
CDLY |
Cooling Interlock delay. Negative value delays fan (or pump)
|
Mins |
0 |
-30 to 30 |
C16 |
FPRD |
Fan Period, minimum time to change fan speed steps |
Secs/10 |
12 |
1 to 60 |
C17 |
FRPT |
Frost Protection
|
- |
0 |
0 to 2 |
C18 |
MANL |
Manual Level, set by Doorway and InSite |
- |
0 |
-100 to 100 |
C19 |
HTSC |
Heat Source |
- |
0 |
-1 to 100 |
C20 |
CLSC |
Cool Source |
- |
0 |
-1 to 100 |
C21 |
HTCT |
Value of CT setpoint sent to Heat Source, % value sent if 0 |
Deg C |
0 |
0 to 100 |
C22 |
CLCT |
Not used, set to 0 in this application |
Deg C |
0 |
0 to 20 |
C23 |
MIDP |
Mid Position
|
% |
0 |
-3 to 99 |
C24 |
TRRG |
Sontay Trim Pot +/- range |
- |
5 |
0 to 10 |
C25 |
ALRM |
Alarm mode
|
- |
1 |
0 to 3 |
C26 |
ALST |
Alarm report sense (used with INMD=4)
|
- |
0 |
0 to 1 |
Monitoring Parameters (3T and 4R versions only) |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
INPA |
Input A status |
- |
- |
0 to 1 |
I2 (C31) |
OCCD |
Occupied |
- |
- |
0 to 1 |
I5 (C34) |
COOL |
Cooling Status |
- |
- |
0 to 1 |
I6 (C35) |
RLYA |
Triac/Relay A Status |
- |
- |
0 to 1 |
I7 (C36) |
RLYB |
Triac/Relay B Status |
- |
- |
0 to 1 |
I8 (C37) |
RLYC |
Triac/Relay C Status |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand; use with MANL to set output level |
- |
0 |
0 to 1 |
W6 (C43) |
POT |
Potentiometer fitted to board |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
Monitoring Parameters (7R versions only) |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
INPA |
Input A status |
- |
- |
0 to 1 |
I2 (C31) |
OCCD |
Occupied |
- |
- |
0 to 1 |
I3 (C32) |
CRSE |
SeaChange diagnostic use (cool raise) |
- |
- |
0 to 1 |
I4 (C33) |
CLWR |
SeaChange diagnostic use (cool lower) |
- |
- |
0 to 1 |
I5 (C34) |
COOL |
SeaChange diagnostic use (heating select) |
- |
- |
0 to 1 |
I6 (C35) |
RLYD |
Relay D (fan 1) Status |
- |
- |
0 to 1 |
I7 (C36) |
RLYE |
Relay E (fan 2) Status |
- |
- |
0 to 1 |
I8 (C37) |
RLYF |
Relay F (fan 3) Status |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
FSWM |
Sontay Fan Switch Mode
|
- |
0 |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand; use with MANL to set output level |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
Monitoring Parameters (all versions) |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
S1* (C50) |
SPLA |
Supply Air Temperature |
Deg C |
- |
- |
S2* (C51) |
RTNA |
Return Air Temperature |
Deg C |
- |
- |
S3* (C52) |
HCOP |
Heat Cool Output Valves |
% |
- |
0 to 100 |
S4 (C53) |
SPSL |
Current Supply Setpoint |
Deg C |
- |
- |
S5 (C54) |
SPRT |
Current Return Setpoint |
Deg C |
- |
- |
S6 (C55) |
HDMD |
Heat Demand from Room Loop |
% |
- |
0 to 100 |
S7 (C56) |
CDMD |
Cool Demand from Room Loop |
% |
- |
0 to 100 |
K1 (C60) |
SPOC |
Occupation Setpoint |
Deg C |
20 |
5 to 35 |
K2 (C61) |
SPNO |
Non-Occupation Setpoint |
Deg C |
10 |
5 to 20 |
K3 (C62) |
SPSV |
Supervised Setpoint from Master Controller |
Deg C |
- |
0 to 35 |
K4 (C63) |
SPTR |
Setpoint Trim |
Deg C |
0 |
-10 to 10 |
K5 (C64) |
FANS |
Fan Speed
|
% |
0 |
-1 to 100 |
K6 (C65) |
MXVA |
Maximum voltage channel A (AOP versions only, to special order)
|
V |
10 |
0 to 10 |
K7 (C66) |
MNVA |
Minimum voltage channel A (AOP versions only, to special order) |
V |
0 |
0 to 10 |
K8 (C67) |
MXVB |
Maximum voltage channel B (AOP versions only, to special order) |
V |
10 |
0 to 10 |
K9 (C68) |
MNVB |
Minimum voltage channel B (AOP versions only, to special order) |
V |
0 |
0 to 10 |
Engineering Parameters; only accessible via Doorway and InSite |
|||||
C83 |
MANL |
Fixed HAND manual |
% |
0 |
-100 to 100 |
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
SENF |
Sensor Failed (when set to 1) |
- |
- |
0 or 1 |
C92 |
EXTN |
Alarm for external input |
- |
- |
0 or 1 |
C93 |
STOP |
STOP alarm received (when set to 1) |
- |
- |
0 or 1 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|