Configuration Tables

Fan Coil Controller
(all versions)

issue 4d1-4d3
changes this issue in RED

FCU / DIN / ...

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SPFC
Occupied Return temperature Setpoint
Deg C
20
10 to 35
C2
SPDB
Setpoint Deadband
Deg C
1
0 to 10
C3
SPTR
Setpoint Trim
Deg C
0
-10 to 10
C4
SPTY
Setpoint type
0: Local from C1, occupancy supervised from master Zone Controller
1: Setpoint (and occupancy) supervised from master Zone Controller
2: Supply temperature control or Driver mode (if no supply sensor fitted) based on Heat/Cool demands from Zone Controller or another Fan Coil
Deg C
1
0 to 2
C5
INMD
Input mode for terminals ‘temp a’ ( 'input a' for 7R )
0: Supply temperature
1: Internal Occupancy AND External Occupation signal (short = occupied)
2: Internal Occupancy OR External Occupation signal
3: External Occupation signal only
4: Alarm Input
-
0
0 to 4
C6
MAXH
Supply maximum heating setpoint
Deg C
30
0 to 90
C7
MINH
Supply minimum heating setpoint
Deg C
20
0 to 90
C8
MAXC
Supply maximum cooling setpoint
Deg C
18
2 to 30
C9
MINC
Supply minimum cooling setpoint
Deg C
10
2 to 30
C10
MIND
Supply minimum demand, used for switching between heating and cooling
-
4
0 to 10
C11
OCCO
When set, controller will only run during the Occupied Period
-
0
0 to 1
C12
HPRD
Heating valve period or minimum time
Secs/10
6
0 to 60
C13
HDLY
Heating interlock delay. Negative value delays fan (or pump)
On after heating starts, positive value causes run-on of fan after heating shuts down
Mins
0
-30 to 30
C14
CPRD
Cooling Valve period or minimum On time
Secs/10
6
1 to 60
C15
CDLY
Cooling Interlock delay. Negative value delays fan (or pump)
On after cooling starts, positive value causes run-on of fan after cooling shuts down
Mins
0
-30 to 30
C16
FPRD
Fan Period, minimum time to change fan speed steps
Secs/10
12
1 to 60
C17
FRPT
Frost Protection
0 = No Action,
1 = Open Heating Valve to 50%
2 = Open Heating Valve to 50% and run fan (pump)
-
0
0 to 2
C18
MANL
Manual Level, set by Doorway and InSite
-
0
-100 to 100
C19
HTSC
Heat Source
-
0
-1 to 100
C20
CLSC
Cool Source
-
0
-1 to 100
C21
HTCT
Value of CT setpoint sent to Heat Source, % value sent if 0
Deg C
0
0 to 100
C22
CLCT
Not used, set to 0 in this application
Deg C
0
0 to 20
C23
MIDP
Mid Position
-1: selects two pipe operation
-2: Two pipe plus electric heater( heating mode only)
-3: Two pipe plus electric heater (heating and cooling mode)
0: normal operation
1 to 99: Mid position for Airside Damper control
%
0
-3 to 99
C24
TRRG
Sontay Trim Pot +/- range
-
5
0 to 10
C25
ALRM
Alarm mode
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on alarm
3: report alarms, shut down all outputs on STOP alarm or sensor fail alarm
-
1
0 to 3
C26
ALST
Alarm report sense (used with INMD=4)
0: Alarm if input = 0 (contact open)
1: Alarm if input = 1 (contact closed)
-
0
0 to 1

Monitoring Parameters (3T and 4R versions only)

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
INPA
Input A status
-
-
0 to 1
I2 (C31)
OCCD
Occupied
-
-
0 to 1
I5 (C34)
COOL
Cooling Status
-
-
0 to 1
I6 (C35)
RLYA
Triac/Relay A Status
-
-
0 to 1
I7 (C36)
RLYB
Triac/Relay B Status
-
-
0 to 1
I8 (C37)
RLYC
Triac/Relay C Status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W5 (C42)
HAND
Manual Hand; use with MANL to set output level
-
0
0 to 1
W6 (C43)
POT
Potentiometer fitted to board
-
0
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1

Monitoring Parameters (7R versions only)

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
INPA
Input A status
-
-
0 to 1
I2 (C31)
OCCD
Occupied
-
-
0 to 1
I3 (C32)
CRSE
SeaChange diagnostic use (cool raise)
-
-
0 to 1
I4 (C33)
CLWR
SeaChange diagnostic use (cool lower)
-
-
0 to 1
I5 (C34)
COOL
SeaChange diagnostic use (heating select)
-
-
0 to 1
I6 (C35)
RLYD
Relay D (fan 1) Status
-
-
0 to 1
I7 (C36)
RLYE
Relay E (fan 2) Status
-
-
0 to 1
I8 (C37)
RLYF
Relay F (fan 3) Status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
FSWM
Sontay Fan Switch Mode
0: Intelligent Occupation switching changing fan switch after hours will bring unit back on. Select AUTO to switch off
1: Forced Occupation if Fan Switch is 1-3
-
0
0 to 1
W5 (C42)
HAND
Manual Hand; use with MANL to set output level
-
0
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1

Monitoring Parameters (all versions)

Doorway / InSite Code

Label

Description

Units

Default Value

Range

S1* (C50)
SPLA
Supply Air Temperature
Deg C
-
-
S2* (C51)
RTNA
Return Air Temperature
Deg C
-
-
S3* (C52)
HCOP
Heat Cool Output Valves
%
-
0 to 100
S4 (C53)
SPSL
Current Supply Setpoint
Deg C
-
-
S5 (C54)
SPRT
Current Return Setpoint
Deg C
-
-
S6 (C55)
HDMD
Heat Demand from Room Loop
%
-
0 to 100
S7 (C56)
CDMD
Cool Demand from Room Loop
%
-
0 to 100
K1 (C60)
SPOC
Occupation Setpoint
Deg C
20
5 to 35
K2 (C61)
SPNO
Non-Occupation Setpoint
Deg C
10
5 to 20
K3 (C62)
SPSV
Supervised Setpoint from Master Controller
Deg C
-
0 to 35
K4 (C63)
SPTR
Setpoint Trim
Deg C
0
-10 to 10
K5 (C64)
FANS
Fan Speed
0 switches Fans OFF and controller to override OFF
1-100 manually selects Fan Speed and sets controller to override ON if not already running
-1 sets Fan Speed to AUTO mode, cancels occupancy override
Current Fan Speed returned when read.
%
0
-1 to 100
K6 (C65)
MXVA
Maximum voltage channel A (AOP versions only, to special order)
V
10
0 to 10
K7 (C66)
MNVA
Minimum voltage channel A (AOP versions only, to special order)
V
0
0 to 10
K8 (C67)
MXVB
Maximum voltage channel B (AOP versions only, to special order)
V
10
0 to 10
K9 (C68)
MNVB
Minimum voltage channel B (AOP versions only, to special order)
V
0
0 to 10
   
Engineering Parameters; only accessible via Doorway and InSite
     
C83
MANL
Fixed HAND manual
%
0
-100 to 100
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
SENF
Sensor Failed (when set to 1)
-
-
0 or 1
C92
EXTN
Alarm for external input
-
-
0 or 1
C93
STOP
STOP alarm received (when set to 1)
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 