DHW Controller
with 3 x Triac Outputs
| Feature Notes |
Configuration Tables | Data Sheet D2 (282kb PDF) s/w version 4c1 |
Wiring | History |
Configuration Tables
Latest released version is 4c1
Document last updated 01/11/2001
Recent features not included on Data sheet are in RED
text
Configuration Parameters
| Doorway / InSite Code | Label | Description | Units | Default Value | Range |
| C1 | SACT | Sensor Action 0: Use temp sensor for control, input 3-4 for high limit/VFC 1: Use average of valid sensor values (INMD = 0) 2: Use maximum of valid sensor values (INMD = 0) 3: Use minimum of valid sensor values (INMD = 0) |
- | 0 | 0 to 3 |
| C2 | SCAL | Sensor Calibration | Deg C | 0 | -5 to 5 |
| C3 | SPMD | Midpoint of Setpoint Adjustment | Deg C | 55 | 10 to 95 |
| C4 | SPRG | Setpoint Adjustment Range | Deg C | 25 | 0 to 50 |
| C5 | SPTY | Setpoint Type 0: Setpoint set locally on parameter K1, occupancy supervised from a master Zone Controller using Time Schedule supervision 1: Setpoint (and occupancy) supervised from master Zone Controller using Setpoint Supervision 2: Setpoint set locally on parameter K1, occupancy controlled by multiple zone controllers using Occupancy Demand |
- | 1 | 0 to 2 |
| C6 | SUMR | Summer Immersion Heater Temperature Immersion enabled if LOFL allows and Outside temp > SUMR |
Deg C | 15 | 0 to 30 |
| C7 | LOFL | Low Flow (used with SUMR) Immersion enabled if SUMR allows and Boiler flow < LOFL |
Deg C | 30 | 10 to 70 |
| C8 | VMDE |
DHW Control Valve Mode |
- | 1 | |
| C9 | XHRS | Hours Extension when Override set from Dooway / InSite | - | 1 | 0 to 8 |
| C10 | FRSE | Fabric/Frost Rise | Deg C | 0 | 0 to 10 |
| C11 | INMD |
Input Mode for input terminals 3 and 4 |
- | 0 | 0 to 5 |
| C12 | MIND | Minimum Demand for occupation output to operate 0: When demand drops to zero, pump continues to run MIND > 1: When demand drops to zero, pump stops |
- | 0 | 0 to 10 |
| C13 | OCCO | Occupied Only (select Optimum Start or Occupation Switch operation) 0: Occupancy starts at Optimum Start time 1: Occupancy starts at Occupation Start time |
- | 0 | 0 to 1 |
| C14 | HPRD | Heating Driver Stroke/Minimum On Time | Secs/10 | Depends on driver | 1 to 240 |
| C15 | HDLY | Heating Interlock Delay | Mins | 0 | -30 to 30 |
| C16 | CPRD | Electric Heating Minimum on Time | Secs/10 | Depends on driver | 1 to 240 |
| C17 | CDLY |
Immersion Heater Interlock Delay |
Mins | 0 | -30 to 30 |
| C18 | FRPT |
Frost Protection Mode |
- | 0 | 0 to 2 |
| C19 | MANL | Manual Level, set by Doorway and InSite | % | 0 | 0 to 100 |
| C20 | STAT | Thermostatic control mode 0: Normal Fuzzy Logic Control 1: Thermostatic action with +/- 4 Deg C deadband |
- | 0 | 0 or 1 |
| C21 | AJST | Adjust Start Time. Offsets DHW start from supervising zone | Hrs | 0.0 | -10 to 10 |
| C22 | AJSP | Adjust Stop Time. Offsets DHW stop from supervising zone | Hrs | 0.0 | -10 to 10 |
| C23 | ALRM | Alarm Mode 0: Ignore alarms 1: Report all alarms to Doorway/InSite, no control action, no flashing Temp indicator 2: Report all alarms, shut down all outputs on alarm 3: Report all alarms, shut down on STOP alarm or local alarm 4: Report all alarms, shut down on STOP alarm only |
- | 0 | 0 to 4 |
| C24 | ALST |
Alarm report sense |
- | 0 | 0 to 1 |
| C25 | HTSC | Heat source | - | 1 | 0 to 8255 |
| C26 | OCDS | Occupation Destination | - | 0 | 0 to 8255 |
| C27 | HTCT | Heating Demand sent as CT | Deg C | 70 | 0 to 100 |
Monitoring Parameters
| Doorway / InSite Code | Label | Description | Units | Default Value | Range |
| I1 (C30) | FRST | Frost Protection Mode (SPNO violated) | - | - | 0 to 1 |
| I2 (C31) | OCC | Occupied | - | - | 0 to 1 |
| I3 (C32) | OSRT | Optimum Start in Operation | - | - | 0 to 1 |
| I4 (C33) | EXTI | External Input State | - | - | 0 to 1 |
| I5 (C34) | HILM | DHW High Limit exceeded | - | - | 0 to 1 |
| I6 (C35) | RLYA | Triac A Status | - | - | 0 to 1 |
| I7 (C36) | RLYB | Triac B Status | - | - | 0 to 1 |
| I8 (C37) | RLYC | Triac C Status | - | - | 0 to 1 |
| W1 (C38) | AUTO | Automatic/Manual Status | - | - | 0 to 1 |
| W2 (C39) | OVRD | Override | - | - | 0 to 1 |
| W5 (C42) | HAND | Manual Hand; use with MANL to set output level | - | 0 | 0 to 1 |
| W6 (C43) | POT | not used in this application | - | 0 | 0 to 1 |
| W7 (C44) | SERV | Service Pin Msg (to Doorway +InSite, self resetting) | - | - | 0 to 1 |
| W8 (C45) | CGST | Configuration Mode Status | - | - | 0 to 1 |
| S1* (C50) | HWT | Hot Water Temperature | Deg C | - | 0 to 95 |
| S2* (C51) | DMND | Control Demand | % | - | 0 to 100 |
| S3 (C52) | HWSP | Hot Water Setpoint | Deg C | - | 10 to 95 |
| S4 (C53) | HTOP | Heating Output to actuator | % | - | 0 to 100 |
| S5 (C54) | OPST | Optimum Start Time | hours | - | 0 to 24 |
| S6 (C55) | OPOK | Optimum Start Completion | hours | - | 0 to 24 |
| S7 (C56) | HWT2 | Hot Water Top Temperature | Deg C | - | 0 to 95 |
| K1 (C60) | SPOC | Occupation Setpoint | Deg C | 55 | 10 to 95 |
| K2 (C61) | SPNO | Non-Occupation Setpoint | Deg C | 10 | 5 to 95 |
| K3 (C62) | SPSV | Supervised Setpoint from Master Controller | Deg C | - | 0 to 95 |
| K4 (C63) | SPMX | Maximum Temperature high limit | Deg C | 0 | 0 to 95 |
| K5 (C64) | MXOS | Maximum Optimum Start time | hours | 6 | 1 to 24 |
| K6 (C65) | MXOF | Maximum Optimum Stop time | hours | 2 | 0 to 4 |
| Engineering Parameters; only accessible via Doorway and InSite | |||||
| C83 | MANL | Used with W5 HAND to position VT Valve manually | % | 0 | 0 to 100 |
| C90 | NOAL | No Alarms; all alarms cleared when set to 1 | 0 or 1 | ||
| C91 | SENF | Sensor Failed (when set to 1) | 0 or 1 | ||
| C92 | RPVF | not used in this application | 0 or 1 | ||
| C93 | EXTN | Volt-Free Contact alarm (when set to 1) | 0 or 1 | ||
| C94 | PMPF | Pump Failed (when set to 1) | 0 or 1 | ||
| C95 | STOP | STOP alarm received (when set to 1) | 0 or 1 | ||
| C160 | OPST | Optimum Start time | hours | - | 0 to 24 |
| C161 | OPOK | Optimum Start Completion | hours | - | 0 to 24 |
| C162 | MXOS | Maximum Optimum Start time | hours | 6 | 1 to 24 |
| C163 | MXOF | Maximum Optimum Stop time | hours | 2 | 0 to 4 |
| C164 | OPTE | Optimum start Error allowed | Deg C | 1 | 0.5 to 5 |
| C180 | DI A | Input 3-4 digital status | - | - | 0 or 1 |
| C181 | DI B | Input 5-6 digital status | - | - | 0 or 1 |
| * 24 hour plots available for these values by default | |||||
| Plotting interval and plotted variable changeable via Doorway or InSite |