Configuration Tables | Data Sheet | Wiring Sec Circ | Wiring Chiller | History |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
NOSP |
Non Occupied Setpoint |
Deg C |
40 |
10 to 50 |
C2 |
MAXF |
Maximum Flow Setpoint |
Deg C |
16 |
5 to 100 |
C3 |
MINF |
Minimum Flow Setpoint |
Deg C |
11 |
1 to 100 |
C4 |
SACT |
Sensor Action |
- |
0 |
0 to 3 |
C5 |
SCAL |
Sensor Calibration |
Deg C |
0 |
-10 to +10 |
C6 |
SPTY |
Setpoint Type (CTU type only) |
- |
0 |
0 to 2 |
Setpoint Type (VTU types only) |
- |
1 |
0 to 2 |
||
C7 |
INMD |
Input Mode for input terminals 3 and 4 temp a |
- |
0 |
0 to 5 |
C8 |
MIND |
Minimum Demand |
% |
5 |
0 to 100 |
C9 |
MNAV |
Minimum Average Demand |
% |
0 |
0 to 100 |
C10 |
MNOC |
Minimum number of Occupied Zones |
- |
0 |
0 to 200 |
C11 |
MNDV |
Minimum demand for driver, affects control of Fan or Pump |
% |
5 |
0 to 100 |
C12 |
GAIN |
Flow Gain added to setpoint and sent to Cooling Provider |
Deg C |
2 |
0 to 20 |
C13 |
CPRD |
Cooling Driver Stroke/Minimum On Time |
Secs/10 |
18 |
1 to 240 |
C14 |
CDLY |
Cooling Interlock Delay |
Mins |
5 - |
30 to 30 |
C15 |
FPRD |
Not used in this application |
Secs/10 |
12 |
1 to 240 |
C16 |
FRPT |
Frost Protection Mode
|
- |
2 |
0 to 3 |
C17 |
MANL |
Manual Level, set by Doorway or InSite |
% |
0 |
-100 to 100 |
C18 |
CMDE |
Control Mode |
- |
1 |
0 to 1 |
C19 |
ALRM |
Alarm Mode |
- |
0 |
0 to 4 |
C20 |
ALST |
Alarm report sense |
- |
1 |
0 to 1 |
C21 |
CLSC |
Cool Source |
- |
0 |
0 to 8255 |
C22 |
OCDS |
Occupation Destination |
- |
0 |
0 to 8255 |
C23 |
CLCT |
Cooling Demand sent as CT
|
- |
1 |
0 to 1 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
EXTI |
External Input (function depends on INMD setting) |
- |
- |
0 to 1 |
I2 (C31) |
OCCD |
Occupied |
- |
- |
0 to 1 |
I4 (C33) |
COND |
Condensation Alarm |
- |
- |
0 to 1 |
I5 (C34) |
COOL |
Cooling Mode |
- |
- |
0 to 1 |
I6 (C35) |
RLYA |
Triac A Status (for 3T types only |
- |
- |
0 to 1 |
I7 (C36) |
RLYB |
Triac B Status (for 3T types only |
- |
- |
0 to 1 |
I8 (C37) |
RLYC |
Triac C Status (for 3T types only |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
ILKP |
Interlock Pump (PCO submodule) |
- |
- |
0 to 1 |
W4 (C41) |
ESTF |
Establish Flow (PCO submodule) |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand; use with MANL to set output level |
- |
0 |
0 to 1 |
W6 (C43) |
POT |
Not used in this application |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Message (to Doorway and InSite, self resetting) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
S1* (C50) |
CTMP |
Chilled Water Temperature |
Deg C |
- |
- |
S2* (C51) |
DMND |
Control Demand |
% |
- |
-100 to 100 |
S3 (C52) |
REQD |
Controller current setpoint |
Deg C |
- |
- |
S4 (C53) |
ZDMD |
Highest demand from zones |
% |
- |
- |
S5 (C54) |
AVDM |
Average demand from zones |
% |
- |
- |
S6 (C55) |
NOCC |
Number of zones Occupied |
- |
- |
- |
S7 (C56) |
FLOW |
Flow Temperature |
Deg C |
- |
- |
S8 (C57) |
RTRN |
Return Temperature |
Deg C |
- |
- |
K1 (C60) |
MAXF |
Maximum Flow Setpoint (for VTU and CTU) |
Deg C |
16 |
10 to 100 |
K2 (C61) |
MINF |
Minimum Flow Setpoint (for VTU only) |
Deg C |
11 |
5 to 100 |
K3 (C62) |
MXVA |
Maximum Voltage output a (for AOP types only) |
Vdc |
10 |
0 to 10 |
K4 (C63) |
MNVA |
Minimum Voltage output a (for AOP types only) |
Vdc |
0 |
0 to 10 |
K5 (C64) |
MXVB |
Maximum Voltage output b (for AOP types only) |
Vdc |
10 |
0 to 10 |
K6 (C65) |
MNVB |
Minimum Voltage output b (for AOP types only) |
Vdc |
0 |
0 to 10 |
Engineering Parameters; only accessible via Doorway and InSite |
|||||
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
SENF |
Sensor Failed (when set to 1) |
- |
- |
0 or 1 |
C92 |
EXTN |
Volt-Free Contact alarm (when set to 1) |
- |
- |
0 or 1 |
C93 |
CNDF |
Condensation detected (when set to 1) |
- |
- |
0 or 1 |
C94 |
PMPF |
Pump Failed (when set to 1) |
- |
- |
0 or 1 |
C95 |
STOP |
STOP alarm received (when set to 1) |
- |
- |
0 or 1 |
C180 |
DI A |
Input 3-4 digital status |
- |
- |
0 or 1 |
C181 |
DI B |
Input 5-6 digital status |
- |
- |
0 or 1 |
* 24 hour plots available for these values by default |
|||||
Plotting interval and plotted variable changeable via Doorway or InSite |