Configuration Parameters
|
Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
C1
|
SACT
|
Sensor Action
0: Use temp sensor for control, input 3-4 for high limit/VFC
1: Use average of valid sensor values (INMD = 0)
2: Use maximum of valid sensor values (INMD = 0)
3: Use minimum of valid sensor values (INMD = 0)
|
-
|
0
|
0 to 3
|
C2
|
SCAL
|
Sensor Calibration
|
Deg C
|
0
|
-5 to 5
|
C3
|
SPMD
|
Midpoint of Setpoint Adjustment
|
Deg C
|
55
|
10 to 95
|
C4
|
SPRG
|
Setpoint Adjustment Range
|
Deg C
|
25
|
0 to 50
|
C5
|
SPTY
|
Setpoint Type
0: Setpoint set locally on parameter K1, occupancy supervised from a master
Zone Controller using Time Schedule supervision
1: Setpoint (and occupancy) supervised from master Zone Controller using
Setpoint Supervision
2: Setpoint set locally on parameter K1, occupancy controlled by multiple
zone controllers using Occupancy Demand
|
-
|
1
|
0 to 2
|
C6
|
SUMR
|
Summer Immersion Heater Temperature
Immersion enabled if LOFL allows and Outside temp > SUMR
|
Deg C
|
15
|
0 to 30
|
C7
|
LOFL
|
Low Flow (used with SUMR)
Immersion enabled if SUMR allows and Boiler flow < LOFL
|
Deg C
|
30
|
10 to 70
|
C8
|
VMDE
|
DHW Control Valve Mode
0: DHW Valve closed until boiler flow temp > DHW temp
1: Boiler flow temp ignored
2: DHW heated from VT circuit (set HTSC Heat Source to 0)
|
-
|
1
|
|
C9
|
XHRS
|
Hours Extension when Override set from Dooway / InSite
|
-
|
1
|
0 to 8
|
C10
|
FRSE
|
Fabric/Frost Rise
|
Deg C
|
0
|
0 to 10
|
C11
|
INMD
|
Input Mode for input terminals 3 and 4
0: Additional temperature input for max, min, ave using SACT
1: External occupation (input linked = Occupied) AND
with internal Occupation
2: External occupation (input linked = Occupied) OR
with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Pump Alarm
|
-
|
0
|
0 to 5
|
C12
|
MIND
|
Minimum Demand for occupation output to operate
0: When demand drops to zero, pump continues to run
MIND > 1: When demand drops to zero, pump stops
|
-
|
0
|
0 to 10
|
C13
|
OCCO
|
Occupied Only (select Optimum Start or Occupation Switch operation)
0: Occupancy starts at Optimum Start time
1: Occupancy starts at Occupation Start time
|
-
|
0
|
0 to 1
|
C14
|
HPRD
|
Heating Driver Stroke/Minimum On Time
|
Secs/10
|
Depends on driver
|
1 to 240
|
C15
|
HDLY
|
Heating Interlock Delay
|
Mins
|
0
|
-30 to 30
|
C16
|
CPRD
|
Electric Heating Minimum on Time
|
Secs/10
|
Depends on driver
|
1 to 240
|
C17
|
CDLY
|
Immersion Heater Interlock Delay
Negative value delays pump after immersion heater starts
Positive value runs pump on after immersion heater stops
|
Mins
|
0
|
-30 to 30
|
C18
|
FRPT
|
Frost Protection Mode
0: No action
1: Open DHW valve 50%
2: Open DHW valve and run pump
|
-
|
0
|
0 to 2
|
C19
|
MANL
|
Manual Level, set by Doorway and InSite
|
%
|
0
|
0 to 100
|
C20
|
STAT
|
Thermostatic control mode
0: Normal Fuzzy Logic Control
1: Thermostatic action with +/- 4 Deg C deadband
|
-
|
0
|
0 or 1
|
C21
|
AJST
|
Adjust Start Time. Offsets DHW start from supervising zone
|
Hrs
|
0.0
|
-10 to 10
|
C22
|
AJSP
|
Adjust Stop Time. Offsets DHW stop from supervising zone
|
Hrs
|
0.0
|
-10 to 10
|
C23
|
ALRM
|
Alarm Mode
0: Ignore alarms
1: Report all alarms to Doorway/InSite,
no control action, no flashing Temp indicator
2: Report all alarms, shut down all outputs on alarm
3: Report all alarms, shut down on STOP alarm or local alarm
4: Report all alarms, shut down on STOP alarm only
|
-
|
0
|
0 to 4
|
C24
|
ALST
|
Alarm report sense
0: Alarm if input = 0 (contact open), pump running if input = 1 (closed)
1: Alarm if input = 1 (contact closed), pump running if input = 0 (open)
|
-
|
0
|
0 to 1
|
C25
|
HTSC
|
Heat source
|
-
|
1
|
0 to 8255
|
C26
|
OCDS
|
Occupation Destination
|
-
|
0
|
0 to 8255
|
C27
|
HTCT
|
Heating Demand sent as CT
|
Deg C
|
70
|
0 to 100
|
C28
|
USEB
|
Use Flow temperature from the main Boiler rather than from own Heat
Source when set to 1
|
-
|
0
|
0 to 1
|
Monitoring Parameters
|
Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
I1 (C30)
|
FRST
|
Frost Protection Mode (SPNO violated)
|
-
|
-
|
0 to 1
|
I2 (C31)
|
OCC
|
Occupied
|
-
|
-
|
0 to 1
|
I3 (C32)
|
OSRT
|
Optimum Start in Operation
|
-
|
-
|
0 to 1
|
I4 (C33)
|
EXTI
|
External Input State
|
-
|
-
|
0 to 1
|
I5 (C34)
|
HILM
|
DHW High Limit exceeded
|
-
|
-
|
0 to 1
|
I6 (C35)
|
RLYA
|
Triac A Status
|
-
|
-
|
0 to 1
|
I7 (C36)
|
RLYB
|
Triac B Status
|
-
|
-
|
0 to 1
|
I8 (C37)
|
RLYC
|
Triac C Status
|
-
|
-
|
0 to 1
|
W1 (C38)
|
AUTO
|
Automatic/Manual Status
|
-
|
-
|
0 to 1
|
W2 (C39)
|
OVRD
|
Override
|
-
|
-
|
0 to 1
|
W3 (C40)
|
PTRN
|
Pasteurisation running
|
-
|
-
|
0 to 1
|
W5 (C42)
|
HAND
|
Manual Hand; use with MANL to set output level
|
-
|
0
|
0 to 1
|
W6 (C43)
|
POT
|
not used in this application
|
-
|
0
|
0 to 1
|
W7 (C44)
|
SERV
|
Service Pin Msg (to Doorway +InSite, self resetting)
|
-
|
-
|
0 to 1
|
W8 (C45)
|
CGST
|
Configuration Mode Status
|
-
|
-
|
0 to 1
|
S1* (C50)
|
HWT
|
Hot Water Temperature
|
Deg C
|
-
|
0 to 95
|
S2* (C51)
|
DMND
|
Control Demand
|
%
|
-
|
0 to 100
|
S3 (C52)
|
HWSP
|
Hot Water Setpoint
|
Deg C
|
-
|
10 to 95
|
S4 (C53)
|
HTOP
|
Heating Output to actuator
|
%
|
-
|
0 to 100
|
S5 (C54)
|
OPST
|
Optimum Start Time
|
hours
|
-
|
0 to 24
|
S6 (C55)
|
OPOK
|
Optimum Start Completion
|
hours
|
-
|
0 to 24
|
S7 (C56)
|
HWT2
|
Hot Water Top Temperature
|
Deg C
|
-
|
0 to 95
|
K1 (C60)
|
SPOC
|
Occupation Setpoint
|
Deg C
|
55
|
10 to 95
|
K2 (C61)
|
SPNO
|
Non-Occupation Setpoint
|
Deg C
|
10
|
5 to 95
|
K3 (C62)
|
SPSV
|
Supervised Setpoint from Master Controller
|
Deg C
|
-
|
0 to 95
|
K4 (C63)
|
SPMX
|
Maximum Temperature high limit
|
Deg C
|
0
|
0 to 95
|
K5 (C64)
|
MXOS
|
Maximum Optimum Start time
|
hours
|
6
|
1 to 24
|
K6 (C65)
|
MXOF
|
Maximum Optimum Stop time
|
hours
|
2
|
0 to 4
|
|
|
Engineering Parameters; only accessible via Doorway and InSite
|
|
|
|
C83
|
MANL
|
Used with W5 HAND to position Valve manually
|
%
|
0
|
0 to 100
|
C90
|
NOAL
|
No Alarms; all alarms cleared when set to 1
|
-
|
-
|
0 or 1
|
C91
|
SENF
|
Sensor Failed (when set to 1)
|
-
|
-
|
0 or 1
|
C92
|
RPVF
|
not used in this application
|
-
|
-
|
0 or 1
|
C93
|
EXTN
|
Volt-Free Contact alarm (when set to 1)
|
-
|
-
|
0 or 1
|
C94
|
PMPF
|
Pump Failed (when set to 1)
|
-
|
-
|
0 or 1
|
C95
|
STOP
|
STOP alarm received (when set to 1)
|
-
|
-
|
0 or 1
|
C96
|
PTCF
|
Pasteurisation Cycle Failed alarm sent(when set to 1)
|
-
|
-
|
0 or 1
|
C160
|
OPST
|
Optimum Start time
|
hours
|
-
|
0 to 24
|
C161
|
OPOK
|
Optimum Start Completion
|
hours
|
-
|
0 to 24
|
C162
|
MXOS
|
Maximum Optimum Start time
|
hours
|
6
|
1 to 24
|
C163
|
MXOF
|
Maximum Optimum Stop time
|
hours
|
2
|
0 to 4
|
C164
|
OPTE
|
Optimum start Error allowed
|
Deg C
|
1
|
0.5 to 5
|
C173
|
PTDW
|
Pasteurisation Day:day of week for pasturisation, monday 1: sunday 7
|
day
|
0
|
1 to 7
|
C174
|
PTST
|
Pasteurisation Start Time, 24 hour clock set to nearest tenth of an
hour
|
hours
|
0.0
|
0.0 to 24.0
|
C175
|
PTPD
|
Pasteurisation Period: time in hours for which the water temperature
needs to be pasturised
must be non zero to activate pasturisation
|
hours
|
0.0
|
0.0 to 4.0
|
C176
|
PTSP
|
Pasteurisation Temperature
must be non zero to activate pasturisation
|
°C
|
0
|
0 to 90
|
C177
|
PTOK
|
Pasteurisation completed correctly
|
-
|
0
|
read only
|
C180
|
DI A
|
Input 3-4 digital status
|
-
|
-
|
0 or 1
|
C181
|
DI B
|
Input 5-6 digital status
|
-
|
-
|
0 or 1
|
|
|
* 24 hour plots available for these values by default
|
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite
|
|
|
|