- type=10
relayA time proportioning control of DHW valve
relay B immersion heater control, needs auxiliary contactor.
- type=11
relay A & B valve positioning control of DHW valve
relay C immersion heater control, needs auxiliary contactor.
The immersion heater is used if Outside Temperature is less than Summer temperature defined by config variable SUMR, default value 15C, and the Boiler Flow temperature (or secondary Heat source) is less than Low Flow temperature defined by LOFL, default value 30C.
The immersion is also used to 'boost' the DHW recovery time if after 15 minutes the Boiler Flow temperature is not higher than the DHW temperature and the DHW control loop is still calling for maximum heat. Boost is disabled if the Outside temperature is above the 'summer temperature'.
- SUMR Summer temperature default 15 see above
- LOFL Low Flow temperature default 30 see above
- VMDO Valve mode which has two settings
- =0 DHW valve stays closed until boiler flow temperature greater than current DHW temperature.
=1 boiler flow temperature ignored, default setting
Label |
Doorway code |
DHW Controller |
FRST |
I1 (C30) |
frost protection |
OCC |
I2 (C31) |
occupied, some demand signal is being received |
WMUP |
I3 (C32) |
Warm up |
OOFF |
I4 (C33) |
Optimum off |
RLYA |
I6 (C35) |
relay A status |
RLYB |
I7 (C36) |
relay B status |
RLYC |
I8 (C37) |
relay C status |
AUTO |
W1 (C38) |
Automatic, control mode |
OVRD |
W2 (C39) |
Override |
CGST |
W8 (C45) |
Configuration mode status |
HW T |
S1 (C50) |
Hot Water temperature |
HWSP |
S2 (C51) |
Hot water setpoint |
TRIM |
S3 (C52) |
Trim heating positive, cooling negative |
HTOP |
S4 (C53) |
Heating output to actuators |
OCSP |
K1 (C60) |
Occupied setpoint |
NOSP |
K2 (C61) |
Non Occupied setpoint |
SVSP |
K3 (C62) |
Supervised setpoint |