Configuration Tables

DHWx3c1

Ref   Description default range
C1 SACT sensor action

0 use local sensor unless remote sensor connected see use of nviRemoteTemp for Open systems

1 average valid sensor values

2 maximum of valid sensor values

3 minimum of valid sensor values

4 use remote sensor as Occupation input , shorted is occupied

5 use nviRemoteTemp if valid, else remote hardwired if valid else local

0 0 to 5
C2 SCAL Calibrate sensor value 0 -5.0 to 5.0C
C3 SPMD Midpoint of setpoint adjustment range 55 10 to 95C
C4 SPRG Range of setpoint adjustment about midpoint 25 0 to 50C
C5 SPTY Setpoint type

0 use local setpoint

1 use remote setpoint, disable local OSS

2 Occupancy control from one or more Zones

1 0 to 2
C6 SUMR Summer temperature, used with LOFL to enable use of the immersion heater 15 0 to 30C
C7 LOFL Low Flow temperature, used with SUMR to enable use of the immersion heater 30 10 to 70C
C8 VMDE Valve mode, controls interaction between wet heating and electric heating

0 DHW valve stays closed until boiler flow temperature greater than current DHW temperature.

1 boiler flow temperature ignored

2 Designed for systems where the DHW is heated from a Variable temperature circuit, if the VT temperature is higher than the DHW temperature it is used otherwise the water circuit is closed and the Electric heater used. Note set heat source to zero for this option because it is not appropriate for the DHW demand to influence the Boiler Controller.

1  
C9 XHRS Extension hours when override pressed outside occupation 1 0 to 8.0
C10 FRSE Sets the temperature rise which will be needed to complete the freezing protection routine 0 0.0 to 10.0C
C11 OCCO When set controller will only run during the occupied period 0 0 to 1
C12 HPRD heating valve period or minimum on time depends on driver type 1 to 240 secs/10
C13 HDLY Interlock delay

negative value delays fan (or pump) after heating starts

positive value cause run on of fan after heating shuts down

0 -30.0 to 30.0 minutes
C14 CPRD electric heating period or minimum on time depends on driver type 1 to 240 secs/10
C15 CDLY electric heating Interlock delay

negative value delays fan (or pump) after cooling starts

positive value cause run on of fan after cooling shuts down

0 -30.0 to 30.0 minutes
C16 FRPT Frost protect

0 no action

1 open heating valve 50%

2 open heating valve and run pump/fan

0 0 to 2
C17 MANL Manual level , from Doorway 0 0 to 100 %
C18 STAT selects thermostatic mode for control 0 0 or 1
C19 AJST start time adjust 0.0 -10.0 to 10.0 hours
C20 AJSP stop time adjust 0.0 -10.0 to 10.0 hours
C21 ALRM alarm mode

0 ignore alarms

1 report alarms

2 report alarms, shut down all outputs on alarm

3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm

1 0 to 3
C22 ALST not used 0 0 to 1
C23 HTSC Heat source 1 -1 to 100

Digital monitoring

ref   Description default range
C30 FRST frost protection mode   0 to 1
C31 OCCD occupied   0 to 1
C32 OSRT optimum start in operation   0 to 1
C33 OOFF optimum off in operation   0 to 1
C34 ---- not used   0 to 1
C35 RLYA relay A   0 to 1
C36 RLYB relay B   0 to 1
C37 RLYC relay C   0 to 1
C38 AUTO Automatic/manual mode   0 to 1
C39 OVRD override   0 to 1
C45 CGST configuration mode    

Sensors

ref   Description default range
C50 HW T DHW temperature   5.0 to 35.0 C
C51 DMND heat output to drivers   0 to 100%
C52 HWSP current setpoint   10.0 to 95.0 C
C53 HTOP heat output to actuators   0 to 100%
C54 OPST Optimum Start time (hours)   0 to 24.0
C55 OPOK Optimum Start complete (OK) (hours)   0 to 24.0

knobs

ref   Description default range
C60 SPOC Occupied setpoint 55.0 10.0 to 95.0 C
C61 SPNO Non Occupied setpoint 10.0 5.0 to 95.0 C
C62 SPSV Supervised setpoint from Master controller   0 to 95.0 C
C63 MXOS Maximum Optimum Start time (hours) 6.0 1 to 24.0
C64 MXOF Maximum Optimum Stop time (hours) 2 0 to 4.0
C65 MXVA* Maximum voltage channel A 10.0 0.0 to 10.0 volt
C66 MNVA* Minimum voltage channel A 0.0 0.0 to 10.0 volt
C67 MXVB* Maximum voltage channel B 10.0 0.0 to 10.0 volt
C68 MNVB* Minimum voltage channel B 0.0 0.0 to 10.0 volt

*AOP models only

loop parameters

ref   Description default range
C70 UNDH sets very Low muzzy level for heating loop 4.0 1.0 to 25.0C
C71 OVRH sets very High muzzy level for heating loop 4.0 1.0 to 25.0C
C72 DBBH deadband sets limit for OK band for heating loop 2.0 5 to 25.0C
C73 RCGH max rate of change heating   1 to 250
C74 GN H gain heating 50 1 to 250

System

ref   Description default range
C80 XCFG forces exit from config mode 0 to 1  
C81 GRP own group number 0 to 255  
C82 HDAY number of days holiday 0 0 to 99

Alarms

ref   Description default range
C90 NOAL no alarm    
C91 SENF sensor fail    
C92 EXTN alarm for external input    
C93 STOP STOP alarm received    

Registration table

ref   Description default range
C100 #ACT number of Actuators registered to this controller 0 0 to 8
C101 HTSC Heat source 1 -1 to 100

Documentation

ref   Description default range
C121 MZON zone number of master zone 0 0 to 200

Plot configuration

ref   Description default range
C130 PN A config variable number for channel A 51 0 to 255
C131 PT A period code for plot A 1 1 to 4
C132 PN B config variable number for channel B 52 0 to 255
C133 PT B period code for plot B 1 1 to 4

Driver Parameter

ref   Description default range
C150 HTYP heating driver type 2 0 to 5
C151 HSTG number of heating stages 1 0 to 8
C152 CTYP cooling driver type 2 0 to 5
C153 CSTG number of cooling stages 1 0 to 8
C154 FTYP fan driver type 6 0 to 7
C155 FSTG number of fan stages 1 0 to 5
C156 MXVA* Maximum voltage channel A 10.0 0.0 to 10.0 volt
C157 MNVA* Minimum voltage channel A 0.0 0.0 to 10.0 volt
C158 MXVB* Maximum voltage channel B 10.0 0.0 to 10.0 volt
C159 MNVB* Minimum voltage channel B 0.0 0.0 to 10.0 volt

Optimum Start Stop

C160 OPST Optimum Start time (hours)   0 to 24.0
C161 OPOK Optimum Start complete (OK) (hours)   0 to 24.0
C162 MXOS Maximum Optimum Start time (hours) 6.0 1 to 24.0
C163 MXOF Maximum Optimum Stop time (hours) 2 0 to 4.0
C164 OPTE Optimum start Error allowance (droop) 1.0 0.5 to 5.0
C165 OPTH Heating Optimisation constant 100 read only
C166 OPTC Cooling Optimisation constant 100 read only
C167 OPTO Optimum off constant 100 read only