| Ref | Description | default | range | |
| C1 | SACT | sensor action 0 use local sensor unless remote sensor connected see use of nviRemoteTemp for Open systems 1 average valid sensor values 2 maximum of valid sensor values 3 minimum of valid sensor values 4 use remote sensor as Occupation input , shorted is occupied 5 use nviRemoteTemp if valid, else remote hardwired if valid else local |
0 | 0 to 5 |
| C2 | SCAL | Calibrate sensor value | 0 | -5.0 to 5.0C |
| C3 | SPMD | Midpoint of setpoint adjustment range | 55 | 10 to 95C |
| C4 | SPRG | Range of setpoint adjustment about midpoint | 25 | 0 to 50C |
| C5 | SPTY | Setpoint type 0 use local setpoint 1 use remote setpoint, disable local OSS 2 Occupancy control from one or more Zones |
1 | 0 to 2 |
| C6 | SUMR | Summer temperature, used with LOFL to enable use of the immersion heater | 15 | 0 to 30C |
| C7 | LOFL | Low Flow temperature, used with SUMR to enable use of the immersion heater | 30 | 10 to 70C |
| C8 | VMDE | Valve mode, controls interaction between wet
heating and electric heating 0 DHW valve stays closed until boiler flow temperature greater than current DHW temperature. 1 boiler flow temperature ignored 2 Designed for systems where the DHW is heated from a
Variable temperature circuit, if the VT temperature is higher than the DHW temperature it
is used otherwise the water circuit is closed and the Electric heater used. Note set heat
source to zero for this option because it is not appropriate for the DHW demand to
influence the Boiler Controller. |
1 | |
| C9 | XHRS | Extension hours when override pressed outside occupation | 1 | 0 to 8.0 |
| C10 | FRSE | Sets the temperature rise which will be needed to complete the freezing protection routine | 0 | 0.0 to 10.0C |
| C11 | OCCO | When set controller will only run during the occupied period | 0 | 0 to 1 |
| C12 | HPRD | heating valve period or minimum on time | depends on driver type | 1 to 240 secs/10 |
| C13 | HDLY | Interlock delay negative value delays fan (or pump) after heating starts positive value cause run on of fan after heating shuts down |
0 | -30.0 to 30.0 minutes |
| C14 | CPRD | electric heating period or minimum on time | depends on driver type | 1 to 240 secs/10 |
| C15 | CDLY | electric heating Interlock delay negative value delays fan (or pump) after cooling starts positive value cause run on of fan after cooling shuts down |
0 | -30.0 to 30.0 minutes |
| C16 | FRPT | Frost protect 0 no action 1 open heating valve 50% 2 open heating valve and run pump/fan |
0 | 0 to 2 |
| C17 | MANL | Manual level , from Doorway | 0 | 0 to 100 % |
| C18 | STAT | selects thermostatic mode for control | 0 | 0 or 1 |
| C19 | AJST | start time adjust | 0.0 | -10.0 to 10.0 hours |
| C20 | AJSP | stop time adjust | 0.0 | -10.0 to 10.0 hours |
| C21 | ALRM | alarm mode 0 ignore alarms 1 report alarms 2 report alarms, shut down all outputs on alarm 3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm |
1 | 0 to 3 |
| C22 | ALST | not used | 0 | 0 to 1 |
| C23 | HTSC | Heat source | 1 | -1 to 100 |
| ref | Description | default | range | |
| C30 | FRST | frost protection mode | 0 to 1 | |
| C31 | OCCD | occupied | 0 to 1 | |
| C32 | OSRT | optimum start in operation | 0 to 1 | |
| C33 | OOFF | optimum off in operation | 0 to 1 | |
| C34 | ---- | not used | 0 to 1 | |
| C35 | RLYA | relay A | 0 to 1 | |
| C36 | RLYB | relay B | 0 to 1 | |
| C37 | RLYC | relay C | 0 to 1 | |
| C38 | AUTO | Automatic/manual mode | 0 to 1 | |
| C39 | OVRD | override | 0 to 1 | |
| C45 | CGST | configuration mode |
| ref | Description | default | range | |
| C50 | HW T | DHW temperature | 5.0 to 35.0 C | |
| C51 | DMND | heat output to drivers | 0 to 100% | |
| C52 | HWSP | current setpoint | 10.0 to 95.0 C | |
| C53 | HTOP | heat output to actuators | 0 to 100% | |
| C54 | OPST | Optimum Start time (hours) | 0 to 24.0 | |
| C55 | OPOK | Optimum Start complete (OK) (hours) | 0 to 24.0 |
| ref | Description | default | range | |
| C60 | SPOC | Occupied setpoint | 55.0 | 10.0 to 95.0 C |
| C61 | SPNO | Non Occupied setpoint | 10.0 | 5.0 to 95.0 C |
| C62 | SPSV | Supervised setpoint from Master controller | 0 to 95.0 C | |
| C63 | MXOS | Maximum Optimum Start time (hours) | 6.0 | 1 to 24.0 |
| C64 | MXOF | Maximum Optimum Stop time (hours) | 2 | 0 to 4.0 |
| C65 | MXVA* | Maximum voltage channel A | 10.0 | 0.0 to 10.0 volt |
| C66 | MNVA* | Minimum voltage channel A | 0.0 | 0.0 to 10.0 volt |
| C67 | MXVB* | Maximum voltage channel B | 10.0 | 0.0 to 10.0 volt |
| C68 | MNVB* | Minimum voltage channel B | 0.0 | 0.0 to 10.0 volt |
*AOP models only
| ref | Description | default | range | |
| C70 | UNDH | sets very Low muzzy level for heating loop | 4.0 | 1.0 to 25.0C |
| C71 | OVRH | sets very High muzzy level for heating loop | 4.0 | 1.0 to 25.0C |
| C72 | DBBH | deadband sets limit for OK band for heating loop | 2.0 | 5 to 25.0C |
| C73 | RCGH | max rate of change heating | 1 to 250 | |
| C74 | GN H | gain heating | 50 | 1 to 250 |
| ref | Description | default | range | |
| C80 | XCFG | forces exit from config mode | 0 to 1 | |
| C81 | GRP | own group number | 0 to 255 | |
| C82 | HDAY | number of days holiday | 0 | 0 to 99 |
| ref | Description | default | range | |
| C90 | NOAL | no alarm | ||
| C91 | SENF | sensor fail | ||
| C92 | EXTN | alarm for external input | ||
| C93 | STOP | STOP alarm received |
| ref | Description | default | range | |
| C100 | #ACT | number of Actuators registered to this controller | 0 | 0 to 8 |
| C101 | HTSC | Heat source | 1 | -1 to 100 |
| ref | Description | default | range | |
| C121 | MZON | zone number of master zone | 0 | 0 to 200 |
| ref | Description | default | range | |
| C130 | PN A | config variable number for channel A | 51 | 0 to 255 |
| C131 | PT A | period code for plot A | 1 | 1 to 4 |
| C132 | PN B | config variable number for channel B | 52 | 0 to 255 |
| C133 | PT B | period code for plot B | 1 | 1 to 4 |
| ref | Description | default | range | |
| C150 | HTYP | heating driver type | 2 | 0 to 5 |
| C151 | HSTG | number of heating stages | 1 | 0 to 8 |
| C152 | CTYP | cooling driver type | 2 | 0 to 5 |
| C153 | CSTG | number of cooling stages | 1 | 0 to 8 |
| C154 | FTYP | fan driver type | 6 | 0 to 7 |
| C155 | FSTG | number of fan stages | 1 | 0 to 5 |
| C156 | MXVA* | Maximum voltage channel A | 10.0 | 0.0 to 10.0 volt |
| C157 | MNVA* | Minimum voltage channel A | 0.0 | 0.0 to 10.0 volt |
| C158 | MXVB* | Maximum voltage channel B | 10.0 | 0.0 to 10.0 volt |
| C159 | MNVB* | Minimum voltage channel B | 0.0 | 0.0 to 10.0 volt |
| C160 | OPST | Optimum Start time (hours) | 0 to 24.0 | |
| C161 | OPOK | Optimum Start complete (OK) (hours) | 0 to 24.0 | |
| C162 | MXOS | Maximum Optimum Start time (hours) | 6.0 | 1 to 24.0 |
| C163 | MXOF | Maximum Optimum Stop time (hours) | 2 | 0 to 4.0 |
| C164 | OPTE | Optimum start Error allowance (droop) | 1.0 | 0.5 to 5.0 |
| C165 | OPTH | Heating Optimisation constant | 100 | read only |
| C166 | OPTC | Cooling Optimisation constant | 100 | read only |
| C167 | OPTO | Optimum off constant | 100 | read only |