Configuration Parameters -  DHW Controller

Types:DHW/DIN/3R/xxx

Software Release: DHWD4a3

Configuration Parameters

Ref   Description default range
C1 SACT sensor action

0 use local sensor unless remote sensor connected see use of nviRemoteTemp for Open systems

1 average valid sensor values

2 maximum of valid sensor values

3 minimum of valid sensor values

4 use remote sensor as Occupation input , shorted is occupied

5 use nviRemoteTemp if valid, else remote hardwired if valid else local

(note: 1-3 only work with 2-input hardware, available to special order)

0 0 to 5
C2 SCAL Calibrate sensor value 0 -5.0 to 5.0C
C3 SPMD Midpoint of setpoint adjustment range 55 10 to 95C
C4 SPRG Range of setpoint adjustment about midpoint 25 0 to 50C
C5 SPTY Setpoint type

0 use local setpoint

1 use remote setpoint, disable local OSS

2 Occupancy control from one or more Zones

1 0 to 2
C6 SUMR Summer temperature, used with LOFL to enable use of the immersion heater 15 0 to 30C
C7 LOFL Low Flow temperature, used with SUMR to enable use of the immersion heater 30 10 to 70C
C8 VMDE Valve mode, controls interaction between wet heating and electric heating

0 DHW valve stays closed until boiler flow temperature greater than current DHW temperature.

1 boiler flow temperature ignored

2 Designed for systems where the DHW is heated from a Variable temperature circuit, if the VT temperature is higher than the DHW temperature it is used otherwise the water circuit is closed and the Electric heater used. Note set heat source to zero for this option because it is not appropriate for the DHW demand to influence the Boiler Controller.

1  
C9 XHRS Extension hours when override pressed outside occupation 1 0 to 8.0
C10 FRSE Sets the temperature rise which will be needed to complete the freezing protection routine 0 0.0 to 10.0C
C11 OCCO When set controller will only run during the occupied period 0 0 to 1
C12 HPRD heating valve period or minimum on time depends on driver type 1 to 240 secs/10
C13 HDLY Interlock delay; defines operation of Pump when LPHW valve is used:

negative value delays  pump after LPHW valve opens

positive value cause run on of pump after valve shuts down

0 -30.0 to 30.0 minutes
C14 CPRD electric heating period or minimum on time depends on driver type 1 to 240 secs/10
C15 CDLY Interlock delay; defines operation of Pump when Immersion Heater is used:

negative value delays pump after Immersion heater starts

positive value cause run on of pump after Immersion heater shuts down

0 -30.0 to 30.0 minutes
C16 FRPT Frost protect

0 no action

1 open heating valve 50%

2 open heating valve and run pump

0 0 to 2
C17 MANL Manual level , from Doorway 0 0 to 100 %
C18 STAT selects thermostatic mode for control

0: Normal Fuzzy Logic Control

1: Thermostatic action; On/off control with +/- 4 degC deadband. Contact SeaChange for narrower deadband operation

0 0 or 1
C19 AJST Start Time Adjust; offsets DHW start time from Supervising Zone's times (e.g. Hot water times earlier than heating times for cleaners etc.)  0.0 -10.0 to 10.0 hours
C20 AJSP Stop Time Adjust; offsets DHW stop time from Supervising Zone's times (e.g. Hot water times later than heating times for cleaners etc.) 0.0 -10.0 to 10.0 hours
C21 ALRM alarm mode

0 ignore alarms

1 report alarms

2 report alarms, shut down all outputs on alarm

3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm

1 0 to 3
C22 ALST not used 0 0 to 1
C23 HTSC Heat source 1 -1 to 100

Monitoring Parameters

ref   Description default range
C30 FRST frost protection mode   0 to 1
C31 OCCD occupied   0 to 1
C32 OSRT optimum start in operation   0 to 1
C33 OOFF optimum off in operation   0 to 1
C34 ---- not used   0 to 1
C35 RLYA relay A status   0 to 1
C36 RLYB relay B status   0 to 1
C37 RLYC relay C status   0 to 1
C38 AUTO Automatic/manual mode   0 to 1
C39 OVRD override   0 to 1
C45 CGST configuration mode    

Sensors

ref   Description default range
S1
(C50)
HW T DHW temperature   5.0 to 35.0 C
S2
(C51)
DMND heat output to drivers   0 to 100%
S3
(C52)
HWSP current setpoint   10.0 to 95.0 C
C53 HTOP heat output to actuators   0 to 100%
C54 OPST Optimum Start time (hours)   0 to 24.0
C55 OPOK Optimum Start complete (OK) (hours)   0 to 24.0

 

Knobs

ref   Description default range
K1
(C60)
SPOC Occupied setpoint 55.0 10.0 to 95.0 C
K2
(C61)
SPNO Non Occupied setpoint 10.0 5.0 to 95.0 C
C62 SPSV Supervised setpoint from Master controller   0 to 95.0 C
C63 MXOS Maximum Optimum Start time (hours) 6.0 1 to 24.0
C64 MXOF Maximum Optimum Stop time (hours) 2 0 to 4.0
C65 MXVA* Maximum voltage channel A 10.0 0.0 to 10.0 volt
C66 MNVA* Minimum voltage channel A 0.0 0.0 to 10.0 volt
C67 MXVB* Maximum voltage channel B 10.0 0.0 to 10.0 volt
C68 MNVB* Minimum voltage channel B 0.0 0.0 to 10.0 volt

* /AOP versions only (to special order)