Configuration Parameters -  Boiler Controller

Types:BLR/DIN/DHW/xxx

Software Release: BLRDM3c9

Configuration Parameters

ref Description default range
C1 HWSP Domestic Hotwater setpoint

 

55 25 to 65
C2 FRST Frost protection level

Can disabled by setting FRST = 0 - (see Data Sheet for details)

3 2 to 15
C3 MAXF Maximum flow water temperature 80 30 to 110
C4 MINR Minimum return water temperature 40 10 to 50
C5 FLAV Heating Flow water temperature at 10°C outside temperature 50 20 to 80
C6 SACT Sensor Action

0 = use flow or return water sensors, if both present use average

1 = use flow water sensor

2 = use return water sensor

3 = average of flow and return water sensors

1 1 to 3
C7 BLRS Total number of boilers/stages in sequence 2 1 to 8
C8 NPMP Total number of pumps 1 1 to 2
C9 MXVT Maximum VT circuit water temperature 60 20 to 100
C10 HWRO Domestic hot water run-on length of time hot water is extended past heating occupation stop time. (e.g. Cleaners, etc) 0 0 to 12
C11 DHWP Domestic hot water priority

0 = Hot water and Heating have equal prioity

1 = Hot water has priority, VT valve will close when water requires heating

0 0 to 1
C12 MIN Boiler minimum run time 5 1 to 20 (minutes)
C13 BRON Primary pump run after all boilers off 1 0 to30

(minutes)

C14 PERD VT circuit valve stroke time 18 (180sec) 2 to 60 secs/10
C15 TRNG Flow setpoint trim, proportional effect from Zone demands 10 0 to 20
C16 CRNG Flow setpoint trim, adaptive effect from Zone demands 10 0 to 20
C17 MODE Zone actuator/valves operation

0 = actuators/valves match their zone heat demand

1 = zone with highest heating demand sets actuator/valve 100%, other zones ratio output dependant on their heat demand. All actuators/valves open fully in BRON period (heat dissaption)

0 0 to 1
C18 BLOK Boiler stages available (i.e.. not in fault condition) 0 to 8
C19 AREM All boilers remote

0 = Boiler outputs on controller are included in sequence

1 = All boiler stages are via cascade modules. Boiler outputs on controller disabled.

0 0 to 1
C20 SMRT Summer heaing inhibit if outside temperature > SMRT 18 10 to 30
C21 MIND Minimum zone demand for boilers to run. 2 0 to 10
C22 COMP Compensator offset 0 -50 to 50
C23 ALRM Alarm mode:

0: No Alarms generated, no control action on event
    1: No Alarms generated, but disable boiler on event
    2: Generate LOKA/B Lockout Alarm and disable boiler
    on fault
    3: Generate GENA/B General Alarm but do not disable boiler          on fault
    4: Generate STOP alarm if input ‘a’ in alarm condition
    (input ‘b’ operates as General alarm)



0


0 to 4
C24 ALST Alarm state

0 = Open circuit indicates Alarm

1 = Closed circuit indicates Alarm


0

0 to 1
C25 TYPE Output type

Not available from Zone Controller (Doorway only). Factory set to:
1 = Normal sequencing of stages

3 = Fixed sequencing of stages

 

1 0 to 8

Monitoring Parameters

ref Description default range
INPUTS
I1 (C30) INPA Fault input 1 status 0 to 1
I2 (C31) INPB Fault input 2 status 0 to 1
I3 (C32) BLRA Boiler 1 output status 0 to 1
I4 (C33) BLRB Boiler 2 output status 0 to 1
I5 (C34) PMPA Pump 1 output status 0 to 1
I6 (C35) PMPB Pump 2 output status  0 to 1
I7 (C36) HTOP Heating output status 0 to 1
I8 (C37) HWOP Hot water output status 0 to 1
SWITCHES
W1

(C38)

AUTO Controller in automatic control 1 0 to 1
W2

(C39)

OVRD Override

W1 and W2 used together with Doorway Auto/manual dialog box

n/a 0 to 1
W3

(C40)

SHOF Summer Heating Inhibit in Operation (Read Only)

1 = Heating disabled

n/a 0 to 1
W4

(C41)

ZBST Zone boost disable - Use weather compensation only.

0 = Zone Boost disabled

1 0 to 1
W6

(C43)

RPLN Replace missing nodes in database

1 = Auto replace node

1 0 to 1
W7

(C44)

SERV Generate Service Pin Message

 

0 0 to 1
W8

(C45)

CGST Configuration mode 0 0 to 1
SENSORS
S1 (C50) FLOW Flow water temperature 0 to 100 °C
S2 (C51) RTRN Return water temperature 0 to 100 °C
S3 (C52) HWTP Domestic hot water temperature 0 to 80 °C
S4 (C53) OUTS Outside temperature 0 to 110 °C
S5 (C54) FLSP Current flow setpoint 0 to 100 °C
S6 (C55) BLOP Current boiler(s) demand level 0 to 100
S7 (C56) HWOP Domestic hot water demand level 0 to 100
S8 (C57) ZDMD Zone demand 0 to 100
KNOBS
K1 (C60) MAXF Maximum flow temperature 80 0 to 100°C
K2 (C61) MINR Minimum return temperature 40 0 to 100°C
K3 (C62) HWSP Domestic hot water setpoint 55 10 to 80°C

 

Control loop parameters

ref   Description default range
C69 FDIV divisor for Boiler flow tracking control 30 5 to 200
C70 UNDF sets very Low muzzy level for boiler loop   9 20 to 200
C71 OVRF sets very High muzzy level for boiler loop 9 20 to 200
C72 DBDF deadband sets limit for OK band for boiler loop 5 20 to 100
C73 RCGF max rate of change primary circuit temp 2 5 to 100
C74 RN F gain boiler 5 1 to 200
C75 UNDV sets very Low muzzy level for VT loop 9 20 to 200
C76 OVRV sets very High muzzy level for VT loop 9 20 to 200
C77 DBDV deadband sets limit for OK band for VT loop 5 20 to 100
C78 RCGV max rate of change variable circuit temp 2 5 to 100
C79 GN V gain variable temperature circuit 5 1 to 200

 

System parameters

ref   Description default range
C80 XCFG Force others exit config n/a 0 to 1
C81 CSTP Enable remote application restart n/a 0 to 99
C82 ADCC Check adc timer still running n/a 0 to 256
C83 APRS Reports number of restarts n/a 0 to 256
C84 NCRS Going deaf number of restarts n/a 0 to 255
C85 SWRS None power up restarts n/a 0 to 256
C86 ADCE adc errors n/a 0 to 255

Alarm parameters

ref   Description default range
C90 NOAL No Alarms n/a 0 to 1
C91 GENA General alarm A n/a 0 to 1
C92 GENB General alarm B n/a 0 to 1
C93 LOKA Lockout alarm A n/a 0 to 1 
C94 LOKB Lockout alarm B n/a 0 to 1
C95 FREZ Danger of freezing alarm n/a 0 to 1
C96 STOP Master stop alarm (firelink) n/a 0 to 1

 

Number of registered devices

ref   Description default range
C100 CAS Numer of Cascade module n/a 0 to 8
C101 ZONE Number of Zone's n/a 0 to 100
C102 PCO Number of Pump change over modules n/a 0 to 3
C103 SUPV Number of Supervisors n/a 0 to 8 
C104 HSC Number of Heat Sources n/a 0 to 20
C105 CSC Number of Cool sources n/a 0 to 20
C106 AHU Number of Air Handlers n/a 0 to 50
C107 OUTS Number of Outside Sensors n/a 0 to 1

 

Own Heat & Cool source parameters

ref   Description default range
C121 HSCN Boilers own heat source number 1 1
C122 CSCN Boilers own cool source number 0 0

Plot parameters

ref   Description default range
C130 PN A config variable number for channel A 51 0 to 255
C131 PT A period code for plot A 1 1 to 4
C132 PN B config variable number for channel B 52 0 to 255
C133 PT B period code for plot B 1 1 to 4